Product Manual Oria Thermostat
EAE KNX Oria Thermostat
Oria Thermostat PM R1.0
©
EAE Technology
www.eaetechnology.com
Sayfa
9
/ 50
Telegram Limit Period Duration
50ms
, 100ms, …, 30sn, 1min
Visible when “Enable Telegram
Limit” enabled. Time period to
check telegram numbers
Maximum Telegram Count in
Period
1..
100
…255
Visible when “Enable Telegram
Limit” enabled. Maximum number
of telegrams to send in telegram
limit period duration
Light Duration of LED
0,75s
, 2.25s, 3.25s
LEDs on duration when status LEDs
used as status indication with
rocker or push buttons.
Rocker Count
2
, 3 ,4
Number of rockers should be
selected compatible with device to
be able to use rockers and push
buttons correctly.
Window Status
Enable/
Disable
Enables communication object
which will be used to detect
window status. When window
detected as open thermostat
automatically enters “Protect
Mode” with error and detected as
close will return to the previous
mode.
LCD Backlight Control
*[1]
Always On
LCD backlight always %100
brightness.
Dimmed After Timeout
Normally %30 brightness, after a
button pressed %100 brightness
for 5 seconds, then returns to %30
brightness
LCD Setpoint Segment
Enable
/Disable
When disabled current setpoint
value will replace temperature
segment on LCD and blink for a
few seconds, otherwise additional
setpoint segment will be used.
Table 2
*[1]
LCD Backlight Control: Additional to the LCD backlight control through “LCD Backlight Control” parameter,
LCD has another method to control backlight. Pressing “Setpoint Decrease Button” for longer than 6 seconds
will dim the backlight to %10 brightness. If the LCD backlight control is selected as “Dimmed After Timeout”,
pressing buttons will no longer have any effect on the backlight brightness. Pressing “Setpoint Increase Button”
for longer than 6 seconds causes the brightness levels to return to normal mode.
4.1.2 Communication Objects
No
Object Name
Function
Data Type
Flags
0
General – In operation Active
1 Bit
DPT 1.002
CT
In operation value (0,1) selected through “In operation bit” parameter will be send via the group address
which is linked to this communication object
49
Window Status
Open/Close
1 bit
DPT 1.009
CWT