Transmitted value
[0…4294967295]
0
…4294967295
Visible when “Long Press Data
Type” selected as “4 byte value
[0…4294967295]”.
Table 23
4.3
Temperature Sensor
Temperature sensor and temperature status parameters should be configured from “Temperature Sensor” tab.
Figure 12
4.3.1 Parameters
Parameter
Function
Description
Temperature Unit
Celsius(
°C
)
/ Fahrenheit(
°F
)
Select temperature unit. After
selection all temperature related
parameters and communication
objects should be enter as
selected unit.
Offset (1/10 K)
-128…
0
…127
Offset value entered here will be
added to measured temperature.
It can be used to compensate for
temperature difference caused by
thermostat placement. Entered
value will be divided by 10.
Cyclic Time (in sec)
10…
30
…65535
Cyclic time period to send
temperature from “Current
Temperature” communication
object.
Send Temperature
Cyclic
/ Cyclic and Change
Selects whether temperature will
be send periodically or periodically
and in case of a change in
temperature. Minimum change
value defined in “Minimum
Difference” parameter.