4.4.5.5 Split Unit
Figure 23
Split unit controller does not directly control temperature, since temperature control is split unit’s
responsibility “Current Temperature” and “Current Setpoint” communication objects should be linked to split
units “Ambient Temperature” and “Setpoint Temperature” communication objects.
4.4.5.5.1
Parameters
Parameter
Setting
Description
Cyclic Interval
1…
5
…255
Time period to send cooling
control value over “Cool Control
Value” communication object.
Send On/Off at Control Mode
Switchover
Enable
/ Disable
Enables “Split Cool”
communication object, can be
used to open/close the split unit
when a control mode change
occurs.
Communication Error Object
Enable /
Disable
Enables “Split Cool Error”
communication object. “True”
telegram from this communication
objects cause thermostat to enter
“Protection Mode” with error. (For
more information Chapter 4.5.2)
Table 47