Installation and Operation 

Instructions for 

 

RS311N

 

 

 

1-Heat / 1-Cool 

Non-Programmable 

Setback Thermostat 

 

   

 

 

for Gas, Electric, & Heat Pump Systems 

 

 

 

 

 

 

 

 

 

www.robertshawclimate.com 

 
 

 

TABLE OF CONTENTS 

Introduction

…………………………………………………

 

Standard Features

………………………………………

... 

Button Operations

…………………………………………

 

Thermostat Locations

……………………………………

.. 

Removing The Thermostat From The Backplate

………

 

Description Of The Dip Switch Functions

………………

 

Features And Settings

……………………………………

 

6-7 

Cover Lock

…………………………………………………

 

Replacing The Thermostat On The Backplate

…………

 

Button Press Combinations

………………………………

 

Keypad Lockout

………………………

..

…………………

Temporary Override

………………………………………

 

Setback Input Terminals – Special Functions..

………

.. 

Changing Fahrenheit (°F) To Celsius (°C)

……………

.. 

10 

Power Failures

……………………………………………

10 

Remote Sensors (Optional)

………………………………

 

10 

Setup Menu

………………………………………………

.. 

10 

Wiring Diagrams

…………………………………………

..  11-16 

Specifications

………………………………………………

 

17 

Sensor Faults

……………………………………………

... 

17 

Description Of Icons

………………………………………

  18-19 

Display

………………………………………………………

 

19 

Warranty

…………………………………………………

....  19-20 

INTRODUCTION 

The RS300N family of Non-Programmable Setback Thermostats 
represents the most advanced solid-state, microcomputer 
temperature control on the market today. The thermostat 
incorporates state-of-the-art technology packaged in an extremely 
low profile designer series case.  They are a direct replacement 
for 300 series and DSL series non-programmable units.  The 
Ultra-Touch push-buttons are combined with an easy-to-read, 
blue backlit full function liquid crystal display to provide the 
ultimate in user friendly operation of the heating and air 
conditioning, including gas, electric, oil and heat pump systems. 
 

STANDARD FEATURES 

 

No batteries required – always remembers setpoints  

 

Integrated electronic heat anticipation  and cooling droop with 
built-in  short cycle equipment  protection 

 

Intelligent Fuzzy Logic staging for efficient operation of 
equipment,  including auxiliary heat  

 

Tamper proof electronic keyboard lockout  with 
programmable override ranges and time

 

 

Automatic, Manual and Recirculation Fan operation

 

 

Adjustable Fan Purge after Heating or Cooling Call

 

 

Automatic Heat/Cool  Changeover, Cooling Only, or Heating 
Only Mode Control

 

 

Adjustable Deadband between Heat and Cool Setpoint in 
Auto Changeover 

 

Dual Heating and Cooling Setpoints for Day (Occupied) and 
Night (Unoccupied) operation

 

 

Adjustable Min/Max Setpoints for Heating and Cooling

 

 

Keypad Lockout with rest/-3°F(1°C) or +/-5°F(2°C) 
setpoint adjustment and 0min to 24Hr override timer with 
automatic return

 

 

Selectable Fahrenheit or Celsius temperature display

 

 

Adjustable Backlight Brightness

 

 

Integrated Installer Setup Menu

 

 

Occupancy Sensor Inputs (use RS-OSC or RS-OSW)

BUTTON OPERATION

 

 
 

 

THERMOSTAT LOCATION 

To ensure proper operation, the thermostat  should be mounted 
on an inside wall in a frequently occupied  area of the space. In 
addition, its position  must be at least 18” (46 cm) from any 
outside wall, and approximately 5’, (1.5 m) above the floor in a 
location with freely circulating  air of an average temperature. 

 

Be sure to avoid the following locations:

 

 

Behind doors or in corners where freely circulating air is 
unavailable

 

 

Where direct sunlight or radiant heat from appliances might 
affect control  operation

 

 

On an outside wall

 

 

Adjacent to, or in line with, conditioned  air discharge grilles, 
stairwells or outside doors

 

 

Where its operation may be affected by steam or water pipes 
or  warm  air  stacks  in  an  adjacent  partition,  or  by  any 
unheated / uncooled area behind the thermostat

 

 

Where its operation may be affected by lighting dimmers next 
to it

 

 

Where its operation will be affected by the supply air of an 
adjacent unit

 

 

Near sources of electrical interference such as arcing relay 
contact

 

REMOVING THE THERMOSTAT FROM THE 
BACKPLATE 

 

 

 

1.  Insert a flat blade screwdriver or coin 1/8” into the slot located 

in the bottom center of the thermostat case and twist 1/4 turn. 
When you feel or hear a click, grasp the case from the bottom 
two corners and separate from the backplate as shown in the 
diagram at the left. Some models require more force than 
others when separating due to the number of terminals used. 

2.  Swing the thermostat out from the bottom. 

3.  Lift the thermostat up and off the backplate. 

4.  Place the rectangular opening in the backplate over the 

equipment control wires protruding from the wall and, using 
the backplate as a template, mark the location of the two 
mounting holes 

NOTE:

 There are several versions of the RS300N thermostat. 

The wiring instructions for the equipment are identical. 

5.  Use the supplied anchors and screws for mounting on drywall 

or plaster; drill two 3/16” (5mm) diameter holes at the marked 
locations; use a hammer to tap the nylon anchors in flush to 
the wall surface and fasten backplate using the supplied 
screws. (Do not over tighten!) 

6.  Connect the wires from your system to the thermostat 

terminals as shown in the wiring diagrams. Carefully dress the 
wires so that any excess is pushed back into the wall cavity or 
junction box. Ensure that the wires are flush to the plastic 
backplate. The access hole should be sealed or stuffed to 
prevent drafts from affecting the thermostat. 

NOTE:

 This product must be supplied from a UL/CSA 

LISTED Class 2 power supply. Operation from other supplies 
may result in a potential fire risk. 
 

Summary of Contents for RS311N

Page 1: ...C or RS OSW BUTTON OPERATION THERMOSTAT LOCATION To ensure proper operation the thermostat should be mounted on an inside wall in a frequently occupied area of the space In addition its position must be at least 18 46 cm from any outside wall and approximately 5 1 5 m above the floor in a location with freely circulating air of an average temperature Be sure to avoid the following locations Behind...

Page 2: ...ng the Setup Menu Recirculation Fan can be set for up to 30 minutes of fan operation per hour Default is 0min Fan Purge Configuration Using the Setup Menu Fan Purge time can be set for up to 60 seconds of fan run after a heating or cooling call in order to release remaining conditioned air into the space Default is 0sec Temperature Calibration De calibration The thermostat is pre calibrated at the...

Page 3: ...e override will last as long as the override timer See TEMPORARY OVERRIDE When the short is removed the thermostat will return to its last state and the communications can again set Day Night operation Set Mode to OFF with CLK Terminals When DIP Switch 2 is in the ON position and the CLK terminals are shorted the thermostat will change to OFF mode and only the FAN button can be used until the shor...

Page 4: ...13 14 15 16 ...

Page 5: ...R LIMITED WARRANTY continued The product is not installed according to the manufacturers instructions and specifications The product has been installed near sources of electromagnetic interference EMI such as arcing relay contacts Owner s Responsibility Provide proof of purchase Provide normal care and maintenance Pay for freight labor and travel Pay for service calls related to product installati...

Reviews: