DESCRIPTION OF THE DIP SWITCH FUNCTIONS 

DIP Switch 1 : GE/HP Operation

 

Place DIP Switch  1 to OFF position  for Gas/Electric furnace 
operation. 

 

Place DIP Switch  1 to ON position  for Heat Pump operation.

 

DIP Switch 2 : CLK Terminal Operation

 

Place DIP Switch  2 to OFF position  t o   allow a short across the 
CLK terminals via contact closure or Robertshaw® Occupancy 
Sensor to engage Night (Unoccupied) operation until released.  
Place DIP Switch  2 to ON position  to allow a short to change the 
thermostat to OFF mode until released. 

DIP Switch 3 : 2 Minute or 4 Minute Minimum Off Times  

When DIP Switch  3 is in the ON position,  the minimum OFF time 
is 2 minutes. When in the OFF position it is set to 4 minutes. The 
system will allow equipment  recovery for 2 or 4 minutes before 
turning on again.  This is also known as short cycle protection. 

 

DIP Switch 4 : Unlocked/Locked  Keypad

 

When DIP Switch  4 is in the ON position,  all buttons are disabled 
with the exception of the UP, DOWN and MODE button. Users 
will be restricted to either a +/-3°F(1°C) or +/-5°F(2°C) range from 
the Day (Occupied) setpoints as defined by DIP Switch  7. Users 
will still be able to alternate between HEAT and COOL.

 

DIP Switch 5 : Plenum Fan Switch /Add-On Heat Pump 

DIP Switch  5 is used to determine when the fan needs to be 
turned on. 

 

Place DIP Switch  5 to OFF and DIP Switch  1 to OFF to have the 
fan turn on immediately when there is a call for heat. (Required 
with electric heat.) 

 

Place DIP Switch  5 to ON and DIP Switch  1 to OFF to have the 
plenum switch operate the fan. 

 

Place DIP Switch  5 to OFF and DIP Switch  1 to ON for normal 
heat pump operation. 

 

Place DIP Switch  5 to ON and DIP Switch  1 to ON for Add-On 
(Dual-Fuel) Heat Pump operation.

 

DIP Switch 6 :  OFF

 

Keep OFF

 

DIP Switch 7 : Temporary Override Adjustment Range

 

Place DIP Switch  7 to OFF to limit temporary adjustments to  
+/-3°F(1°C). 

 

Place DIP Switch  7 to ON limit temporary adjustments to  
+/-5°F(2°C) .

 

DIP Switch 8 : Remote Sensor Operation

 

Place DIP Switch  8 to OFF to only use the remote indoor sensor 
(10-528 or RS300-528) for temperature control.  
Place DIP Switch  8 to ON to average the thermostat’s internal 
sensor with the remote indoor sensor(s). 

NOTE:

 If no remote sensor is used, the thermostat will default to 

the thermostat sensor regardless of the DIP Switch setting. 
 

FEATURES AND SETTINGS 

Random Restart

 

After a power failure, the thermostat will delay the heating/ cooling 
equipment start-up by 8-40 seconds. When multiple Robertshaw® 
RS300N thermostats are used, this minimizes the ‘in rush’ current 
(electric power usage) as it reduces the number of HVAC units 
that will be turned on simultaneously. 
 

Override Timer Configuration

 

The length of a temporary override can be adjusted from 0 
minutes to 24 hours, in 10 minute increments. (0 minutes is a 
complete lockout). The default override time is 8 hours. To 
display/set the Override time, either use the integrated setup 
menu or press the MODE and DAY/NIGHT buttons 
simultaneously, then press the UP or DOWN button. 
 

Recirculation Fan Configuration

 

Using the Setup Menu, Recirculation Fan can be set for up to 30 
minutes of fan operation per hour. 
Default is 0min. 
 

Fan Purge Configuration

 

Using the Setup Menu, Fan Purge time can be set for up to 60 
seconds of fan run after a heating or cooling call in order to 
release remaining conditioned air into the space.  
Default is 0sec. 
 

Temperature Calibration (De-calibration)

 

The thermostat is pre-calibrated at the factory, but in some 
installations, lack of airflow at the sensor or proximity to other 
warming or cooling source may cause the temperature to be off 
by a few degrees. To adjust the room temperature reading (with 
or without a remote indoor sensor connected), press and hold 
the Fan button for 12 seconds. The display will then show the 
room temp with 0.06F degree resolution. Press the UP or 
DOWN button to make the adjustment. Press the RESUME 
button to store the new value. To restore the thermostat to 
factory calibration, while in calibration mode, press the MODE 
button to reset and then the RESUME button to store. 
 

 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

FEATURES AND SETTINGS, continued

 

 

COVER LOCK 

You also may lock the cover down to prevent unauthorized 
access to the thermostat by adding the clear plastic lock (included 
in the installation bag). To install, remove the thermostat from the 
backplate and place the clear plastic lock in the backplate as 
shown below. Replace the thermostat and close the cover. The 
cover now is locked. To open, simply use a screwdriver to 
carefully push the lock back, allowing the cover to open. To 
remove the lock, open the cover, remove the thermostat from the 
backplate, and then remove the lock. 

 

 

 

 

 

REPLACING THE THERMOSTAT ON THE 
BACKPLATE 

1.  Position the thermostat on the hinged tabs located at the top 

of the backplate. 

2.  Gently swing the thermostat down and press on the bottom 

center edge until it snaps in place. 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BUTTON PRESS COMBINATIONS 

Single Press 

 

 

MODE 

Changes from COOL to HEAT to 
AUTO to OFF. 

 

 

FAN 

Sets the fan ON (continuous), or AUTO 
(operates with the equipment), or CIRC 
(recirculation). 

 

 

RESUME 

When the keypad is locked, cancels 
temporary setpoint overrides and 
resumes previous operating mode. 

 

 

DAY/NIGHT 

Alternates between Day (Occupied) 
and Night (UnOccupied) setpoints. 

 

 

UP 

Increments the blinking numerical or 
icon segments of the display. 

 

 

DOWN 

Decrements the blinking numerical or 
icon segments of the display. 

 

Multi-Press 

 

 

UP & DOWN 

Toggles between °F and °C. 

 

 

 

FAN & 
DAY/NIGHT 

Changes backlight setting. On, dim or 
off. (After 15 seconds of inactivity) 

 

 

MODE & 
DAY/NIGHT 

Changes the Override Timer. Press 
both, then press UP or DOWN to 
change the override time from 0 
minutes to 24hrs in 10 minute 
increments 

 

 

PRESS & HOLD (12 seconds unless stated otherwise) 

 

 

UP & Down 
 
 

 

MODE 

(HOLD for 2 seconds) 
Enters the Setup Menu 
 
Resets the thermostat to factory 
defaults. Press and hold the MODE 
button to show the number of resets. 
Press the MODE button a second time 
to reset the defaults. 

 

 

FAN 

Enters thermostat sensor de-calibration 
mode. Allows a temperature offset of 
up to +/-6°F. To remove the de-
calibration, press and hold the MODE 
button. 

 

 

 

MODE & 
RESUME 

Allows for adjustment of High and Low 
balance points when displaying outdoor 
temperature (hold for 5 seconds). 
NOTE: There must be an outdoor 
sensor attached for this feature to be 
available. 

Summary of Contents for RS311N

Page 1: ...C or RS OSW BUTTON OPERATION THERMOSTAT LOCATION To ensure proper operation the thermostat should be mounted on an inside wall in a frequently occupied area of the space In addition its position must be at least 18 46 cm from any outside wall and approximately 5 1 5 m above the floor in a location with freely circulating air of an average temperature Be sure to avoid the following locations Behind...

Page 2: ...ng the Setup Menu Recirculation Fan can be set for up to 30 minutes of fan operation per hour Default is 0min Fan Purge Configuration Using the Setup Menu Fan Purge time can be set for up to 60 seconds of fan run after a heating or cooling call in order to release remaining conditioned air into the space Default is 0sec Temperature Calibration De calibration The thermostat is pre calibrated at the...

Page 3: ...e override will last as long as the override timer See TEMPORARY OVERRIDE When the short is removed the thermostat will return to its last state and the communications can again set Day Night operation Set Mode to OFF with CLK Terminals When DIP Switch 2 is in the ON position and the CLK terminals are shorted the thermostat will change to OFF mode and only the FAN button can be used until the shor...

Page 4: ...13 14 15 16 ...

Page 5: ...R LIMITED WARRANTY continued The product is not installed according to the manufacturers instructions and specifications The product has been installed near sources of electromagnetic interference EMI such as arcing relay contacts Owner s Responsibility Provide proof of purchase Provide normal care and maintenance Pay for freight labor and travel Pay for service calls related to product installati...

Reviews: