KEYPAD LOCKOUT 

When DIP Switch #4 is ON, the keypad is locked and temporary 
adjustment to the setpoints are restricted to a setpoint range of  
+/-3°F(1°C) or +/-5°F(2°C) from the Day (Occupied) setpoints for 
the amount of time set in the override timer. 

 

TEMPORARY OVERRIDE  
(in KEYPAD LOCKOUT MODE)

 

Change the temperature setting temporarily without affecting the 
Day (Occupied) and Night (Unoccupied) setpoints, even though 
the keypad is locked. 

 

Press the UP or DOWN button.  If running in Day (Occupied), 
the current occupied setpoint will be shown, and if running in 
Night (Unoccupied), the current occupied setpoint will be 
shown. 

 

Press the UP or DOWN button again.  The current Day 
(Occupied) setpoint will be shown and an Override will be 
started.  If in AUTO mode, press the MODE button to switch 
between heating and cooling setpoints. 

 

Press the UP or DOWN button again to adjust the 
temperature up to the maximum of +/-3°F(1°C) or +/-5°F(2°C) 
for the duration of the override time. 

 

To cancel, simply press the RESUME button. 

 

SETBACK INPUT TERMINALS

 

The CLK terminals allow for two powerful methods to operate the 
thermostat in special conditions when an external stimulus is used 
to short the CLK1/CLK2 terminals. This allows an external time 
clock or other external relay, or a Robertshaw® Occupancy 
Sensor to be incorporated into the control. 

 

Setback with No Override 

With DIP Switch 2 in the OFF position, DIP Switch 4 in the 
OFF position (Keypad Unlocked), and then the CLK terminals 
are shorted, the thermostat will lock into Night (Unoccupied) 
operation (and setpoints) as long as the terminals are 
shorted. Keypad DAY/NIGHT presses and will be ignored 
until the short is removed.  

 

Setback with Override 

With DIP Switch 2 in the OFF position, DIP Switch 4 in the 
ON position (Keypad Locked), and then the CLK terminals are 
shorted, the thermostat will go into Night (Unoccupied) 
operation (and setpoints) as long as the terminals are 
shorted. Keypad DAY/NIGHT presses and will be ignored 
until the short is removed, but an override to Day (Occupied) 
setpoints can be achieved by pressing the UP or DOWN 
buttons.  The override will last as long as the override timer. 
See ‘TEMPORARY OVERRIDE’. When the short is removed, 
the thermostat will return to its last state and the 
communications can again set Day/Night operation. 

 

 

Set Mode to OFF with CLK Terminals 

When DIP Switch 2 is in the ON position and the CLK 
terminals are shorted, the thermostat will change to OFF 
mode and only the FAN button can be used until the short is 
removed.  This feature allows a 3

rd

 party set of contacts (such 

as door or window sensors) to be connected to the CLK 
terminals to shut down the HVAC equipment when a door or 
window is open.  The installer is responsible for any 
necessary time delay to be added to the contacts as needed 
to perform the desired function. When the short is removed, 
the thermostat will revert to its previous operation. 

 

CHANGING FAHRENHEIT (°F) TO CELSIUS (°C) 

To change between °F and °C, use the integrated set up menu or 
simultaneously press the UP and DOWN buttons. The display will 
change automatically. 

 

POWER FAILURES 

This Robertshaw® thermostat  product  will maintain the operation 
settings during any type of power failure. When power is restored 
the thermostat  will return to the last MODE (Heat, Cool, Auto, Off) 
and the DAY (Occupied) setpoints.  If the CLK terminals are 
shorted at power up, the thermostat will operate using the last 
NIGHT (Unoccupied) setpoints.

 

 

SETUP MENU 

The RS300N family of thermostats has an integrated Setup Menu, 
allowing quick access to the following setup functions.  To access 
the menu, simultaneously press and Hold the UP and DOWN 
buttons for seconds.  When the display changes, use the UP or 
DOWN buttons to select the option needed, the MODE button to 
go to the next setup function, and the RESUME button to save 
and exit.  If there are no additional button presses for 15 seconds, 
the thermostat will store, exit and return to normal operation. All 
settings are stored in non-volatile memory. 

 

Setup Menu Order: 

1. 

°F or °C Temperature Display 

2. 

Backlight Brightness Level: On, Low, or Off 

3. 

Mode Options:  Automatic Changeover, Cooling 
Only or Heating Only 

4. 

Min/Max Setpoint Range: Heat High, Heat Low, 
Cool High, Cool Low 

5. 

Calibration: For creating a temperature offset 

6. 

Fan Recirculation: 0min to 30min per hour 

7. 

Fan Purge: 0sec to 60sec after call 

8. 

Override Timer: Set from 0min to 24Hr 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

Summary of Contents for RS311N

Page 1: ...C or RS OSW BUTTON OPERATION THERMOSTAT LOCATION To ensure proper operation the thermostat should be mounted on an inside wall in a frequently occupied area of the space In addition its position must be at least 18 46 cm from any outside wall and approximately 5 1 5 m above the floor in a location with freely circulating air of an average temperature Be sure to avoid the following locations Behind...

Page 2: ...ng the Setup Menu Recirculation Fan can be set for up to 30 minutes of fan operation per hour Default is 0min Fan Purge Configuration Using the Setup Menu Fan Purge time can be set for up to 60 seconds of fan run after a heating or cooling call in order to release remaining conditioned air into the space Default is 0sec Temperature Calibration De calibration The thermostat is pre calibrated at the...

Page 3: ...e override will last as long as the override timer See TEMPORARY OVERRIDE When the short is removed the thermostat will return to its last state and the communications can again set Day Night operation Set Mode to OFF with CLK Terminals When DIP Switch 2 is in the ON position and the CLK terminals are shorted the thermostat will change to OFF mode and only the FAN button can be used until the shor...

Page 4: ...13 14 15 16 ...

Page 5: ...R LIMITED WARRANTY continued The product is not installed according to the manufacturers instructions and specifications The product has been installed near sources of electromagnetic interference EMI such as arcing relay contacts Owner s Responsibility Provide proof of purchase Provide normal care and maintenance Pay for freight labor and travel Pay for service calls related to product installati...

Reviews: