Product Manual Oria Thermostat
EAE KNX Oria Thermostat
Oria Thermostat PM R1.0
©
EAE Technology
www.eaetechnology.com
Sayfa
28
/ 50
Minimum Difference (1/10 K)
1
…255
Only visible if “Send Temperature”
selected as “Cyclic and Change”.
Selects minimum change in
temperature that will trigger
transmission of temperature.
Table 24
4.3.2 Communication Objects
No
Object name
Function
Data Type
Flags
55
Current Temperature
(°C)
Temperature
2 byte
DPT 9.001
CRT
Current Temperature
(°F)
Temperature
2 byte
DPT 9.027
CRT
Communication objects DPT should be decided according to the selected temperature unit. Temperature
telegrams will be send when a temperature change defined at “Minimum Difference” parameter occurs or
cyclic time period overflows.
Table 25
4.4
Thermostat
Figure 13
Parameters related to thermostat control should be configured in this tab. Whether thermostat will be used for
heating, cooling or both should be selected here. When heat/cool control activated a new tab will be open