Product Manual Oria Thermostat
EAE KNX Oria Thermostat
Oria Thermostat PM R1.0
©
EAE Technology
www.eaetechnology.com
Sayfa
40
/ 50
4.4.5.2.2
Communication Objects
No
Object Name
Function
Data Type
Flags
61
Cool Control Value Send
1 bit
DPT 1.002
CT
Cooling actuator will be controlled through this communication object.
Table 42
4.4.5.3 On/Off
Figure 21
Cooling control parameters for on/off controller type should be configured here.
4.4.5.3.1
Parameters
Parameter
Setting
Description
Cyclic Interval
1…
5
…255
Time period to send cooling
control value over “Cool Control
Value” communication object.
Inverse Output
Enable /
Disable
Invert the output of the controller.
For example if normal output is
“On”, then inverted output is
“Off”.
Hysteresis (1/10 K)
1…
30
…255
Hysteresis value (Chapter 4.4.3.3)
Table 43
4.4.5.3.2
Communication Objects
No
Object Name
Function
Data Type
Flags
61
Cool Control Value Send
1 bit
DPT 1.002
CT
Cooling actuator will be controlled through this communication object.
Table 44