Product Manual Oria Thermostat
EAE KNX Oria Thermostat
Oria Thermostat PM R1.0
©
EAE Technology
www.eaetechnology.com
Sayfa
49
/ 50
4.6
Status
Figure 26
4.6.1 Parameters
Status parameter can be used to enable/disable additional control mode status telegrams. Status telegrams
operate the same way as switchover telegrams. But instead of sending switchover telegrams as DPT 1.100 or
DPT 20.105, sends 1 bit On/Off (DPT 1.002) telegrams.
Parameter
Setting
Description
Heating Status
Enable /
Disable
Enable additional heating status
communication object.
Cooling Status
Enable /
Disable
Enable additional cooling status
communication object.
Table 51
4.6.2 Communication Objects
No
Object Name
Function
Data Types
Flags
64
Status Heat
On/Off
1 bit
DPT 1.002
CRT
Heating status will be send through this communication object. (0 : Heating Off, 1 : Heating On)
65
Status Cool
On/Off
1 bit
DPT 1.002
CRT
Cooling status will be send through this communication object. (0 : Cooling Off, 1 : Cooling On)
Table 52