20
for
Selecting a safety level.
From Ready status
rdy
This adjusts the force level, over and above the nominal gate
resistance, needed to trigger the safety overload routines.
Level 1 being the most sensitive and 8 being the least sensi-
tive. The factory default is level 3.
Action
Response
Description
Display
Buzzer
Gate
To enter the program menu.
Press and hold the
button
until buzzer beeps.
Display and buzzer
confirms.
pr9
Scroll < or > to select the
collision force setup option.
Display scrolls
through options.
for
With “For” on the display,
press and release
.
Display shows current
option status.
003
Scroll < or > to the required
setting.
Display changes
respectively.
006
With required setting
displayed, press and release
.
Display briefly shows
the new setting is
saved.
006
After display confirms new
setting.
006
Display returns to
programming menu
options list.
for
x2
x1
x2
Scroll left or right to next
program option.
OR
EXIT back to Ready
status
rdy
irb
Safety infra-red beams setup.
From Ready status
rdy
Use this option to enable the safety beam circuit. The safety
beams circuit must be configured as per page 15 with the
end of line resistor installed.
Action
Response
Description
Display
Buzzer
Gate
To enter the program menu.
Press and hold the
button
until buzzer beeps.
Display and buzzer
confirms.
pr9
Scroll < or > to select the
beam setup option.
Display scrolls
through options.
irb
With “irb” on the display,
press and release
.
Display shows current
option status.
off
Scroll < or > to toggle
between “on” or “off”.
Display changes
respectively.
on
With required setting
displayed, press and release
.
Display briefly shows
the new setting is
saved.
on
After display confirms new
setting.
Beam Setup
Enabled Saved
Display returns to
programming menu
options list.
irb
x2
x1
x2
Scroll left or right to next
program option.
OR
pr9
EXIT back to standby
status