Configuration
25
© 2012 DynaGen Technologies Inc.
TOUGH Series User Manual
4.2
Switched Inputs
The controller is equipped with inputs that respond to contact openings and closures. Each switched
input has the following the options associated with it.
Trigger Modes
Trigger modes signify the conditions that will activate an input.
TRIGGER
DESCRIPTION
Close to +Battery
Input active when +Battery is applied.
Close to Ground
Input active when ground is applied.
Close to +Battery / Ground
Input active when +Battery or ground is applied.
Open
Input active when open (nBattery or ground is applied).
Active Modes
Actives modes are the modes in which an input is capable of being triggered.
ACTIVE
DESCRIPTION
Disable
Input is not active and cannot be triggered.
Global
Input active in every mode with the exception of menu system.
Not In Auto
Input active when controller is not in Auto mode.
Auto
Input active when controller is in Auto mode.
Running
Input active from start signal to engine shutdown.
Cranking
Input active from start signal to engine started.
After Cranking
Input active from engine started to engine shutdown.
NOTE
: All switched inputs with the exception of the the
have actives
modes that are fixed and cannot be changed.