Configuration
34
© 2012 DynaGen Technologies Inc.
TOUGH Series User Manual
Mode Settings
Mode Settings are used to change the way the selected Aux Sensor mode functions. Active Time, Start
Level, and Stop Level do not apply to the 'Fault Monitor' mode.
SETTINGS
DESCRIPTION
Bypass Time
The number of seconds to ignore warnings and failures for that sensor
after the engine has started.
Active Time
The amount of time to turn on the output or engine. See the
'Scenarios' below for more information.
Start Level
The level at which the auxiliary switched output or generator turns on.
Stop Level
The level at which the auxiliary switched output or generator turns off.
Scenarios
The Aux Sensor settings can be configured in such a way that it can provide different 'Scenarios' based
on what the Stop Level and Active time are set to. Refer to the table below to choose the scenario best
suited for your application.
STOP LEVEL
ACTIVE TIME
DESCRIPTION
Disabled
Disabled
Once the Start Level is reached, the output or engine will
turn on indefinitely.
Disabled
Enabled
Once the Start Level is reached, the output or engine will
turn on until Active time expires.
Enabled
Disabled
Once the Start Level is reached, the output or engine will
turn on until the Stop Level is reached.
Enabled
Enabled
Once the Start Level is reached, the output or engine will
turn on until the Stop Level is reached or Active Time
expires.
NOTE
: Once the output or engine turns off, the controller will continue to monitor the levels
and will
restart
the output or engine if the Stop Level still has not been met.