Configuration
30
© 2012 DynaGen Technologies Inc.
TOUGH Series User Manual
FUNCTION
ACTIVE MODE
DESCRIPTION
Recharging
Running
Turns on when the controller is performing a
battery recharge. See
for more information.
Configurable Warnings
and Failures
Configurable
Turns on when corresponding switched input
becomes active. See
for
more information.
Pull Coil
Running
See
for more information.
The following outputs turn on during the event in which they describe. Example: 'High Temp Warn' output
only comes on if there is a warning due to high engine temperature.
OTHER OUTPUTS
High Fuel Warn
Low Oil Pres Warn
Low Fuel Fail
AC Hz Warning
Low Temp Warn
Under RPM Fail
Low Fuel Warn
Under Volt Warn
High Temp Fail
Under RPM Warn
Battery Warn
Over Volt Warn
High Temp Warn
Over RPM Fail
Battery Fail
AC Hz Failure
Low Oil Pres Fail
Over RPM Warn
Coolant Lv Fail
Fuel In Basin
AMF / ATS Outputs
FUNCTION
ACTIVE MODE
DESCRIPTION
Generator Coil
Global
Turns on to move the transfer switch into the
generator position. See
for more
information.
Mains Coil
Global
Turns on to move the transfer switch into the
utility position. See
for more
information..
4.3.1
Pull and Hold Coil
On some engine systems the fuel pump has two solenoids. The reason for this is that the initial power
on of the fuel solenoid requires substantial current (Pull Coil), but only needs a small amount of current
to hold it in place (Hold Coil).
1. Pull coil is energized when fuel is first turned on.
2. Hold coil is energized after pull coil has fully activated.
3. Pull coil is de-energized while Hold coil remains on while the engine is running.
Configuring a switched output to Pull Coil automatically configures the engine logic necessary for a Pull
Coil system.
37
28
30
39