Using The Controller
16
© 2012 DynaGen Technologies Inc.
TOUGH Series User Manual
LED Indicators (C)
The LED indicators are used to display the current status of the system. Different versions of the
TOUGH series controllers have different LED combinations therefore some symbols may not appear on
your controller. The following table shows the meanings of each symbol and LED color.
SYMBOL
FUNCTION
LED STATUS
DESCRIPTION
Generator Status
Solid Green
Engine Running
Solid Amber
Warning
Solid Red
Failure
Mains Status
Solid Green
Mains Available
Solid Red
Mains Unavailable
Load
Symbol Only
Symbol Only
Switch Position
Solid Green
Switch Active
Functional Buttons (D)
The following table describes the function of the Functional Buttons. Keep in mind that some buttons
may have multiple purposes depending on the status of the controller.
SYMBOL
FUNCTION
DESCRIPTION
Off
Used for turning off the engine or exiting out of AUTO mode.
All automatic methods of starting the engine are disabled.
Auto
Places the controller in AUTO mode which allows it to start
or stop based on conditions (Exerciser, Low Battery
Recharge, Failure, Remote Start, Loss of Mains).
Run
Starts the engine manually and will continue to run until the
off button is pressed, emergency stop input is activated, or
a failure occurs.