Configuration
35
© 2012 DynaGen Technologies Inc.
TOUGH Series User Manual
Auxiliary Analog Example
The following section outlines an example of setting up the controller to work with a fan that turns on
(Switched Output B) at an engine temperature of 325°F to cool down the engine. The fan won't turn off
until the engine temperature falls below 200°F. The following flowchart depicts the simplified logic
sequence of the controller.
The settings and graph below gives a general idea of how to configure the controller and how it functions.
As you can see the output turns on at 325°F and stays on until it drops below 200°F. The 'Run Time'
shown here is the amount of time the fan was on.
SETTING
VALUE
REASON
Switched Output B
Aux Sensor 1
This output will be connected to the slave relay
controlling the fan.
Aux Signal Source
Port D
This is the port the engine temperature sensor
will be connected to.
Mode Select
Output on High
The output is to turn on at a high engine
temperature.
Active Time
Disabled
The output is to stay on as long as the Stop Level
has not been reached.
Start Level
325°F
The temperature at which to turn the fan on.
Stop Level
200°F
The temperature at which to turn the fan off.