The function of the input is how the controller responds to that input being triggered. Read the
descriptions in the tables below for the meaning of each function.
FUNCTION
ACTIVE MODE
DESCRIPTION
Disable
N/A
Disables the input regardless of condition.
Start / Stop
Auto / Running
Starts engine when activated and stops engine
when de-activated. Special 'momentary' mode
can also be used, see
for more information.
Emergency Stop
Global
Shuts down the engine immediately. Required to
be wired to cut fuel to the engine. See
for more
information.
Idle Mode
Running
All failures associated with under voltage, under
frequency and under speed are ignored.
Volt Select 1
OFF / Auto
Used for selecting different voltage configurations.
See
for more information.
Volt Select 2
Charger Fault
Global
Displays a warning that there is a charger fault.
Momentary Start
Auto
Starts the engine when momentarily activated.
Momentary Stop
Running
Stops the engine when momentarily activated.
Configurable Warning 1
Configurable
Displays a warning with custom user text. See
for more information.
Configurable Warning 2
Configurable Failure 1
Configurable
Enters a failure mode and displays custom user
text. See
for more
information.
Configurable Failure 2
Air Pressure Failure
Cranking
Enters a failure mode and displays that there is a
low air pressure failure.
Hydraulic Pressure
Failure
Cranking
Enters a failure mode and displays that there is a
low hydraulic pressure failure.
Low Oil Pres Warn
Running
Displays a warning that there is low oil pressure.
Coolant Level Failure
Global
Enters a failure mode and displays that there is a
low coolant failure.
High Fuel Warning
Global
Displays a warning that the fuel level is too high.
Lamp Test
Global
Performs a 'Lamp Test' for the LED's.
Fuel In Basin
Global
Displays a warning that there is fuel in the basin.
Battle Mode
Running
Ignores all warnings and failures while running.