START-UP CHECK LIST
Date ______________
YES
NO
Unit Model No.
_________________________
Setting Unit:
a. Vibration isolator used
_________
_________
b. Spring isolator adjusted for equal heiqht
_________
_________
c. If rubber-in-shear isolators are used, is unit leveled by shimming
_________
_________
Wiring:
a. Power wiring complete
_________
_________
b. Control wiring complete
_________
_________
c. Electric service adequate for load
_________
_________
d. Power source voltage correct for motor(s) used
_________
_________
e. Motor circuit has proper size fusetrons
_________
_________
f. System wired per diagram
_________
_________
g. All wire connections tight
_________
_________
h. Wiring complies with local codes
_________
_________
i. Flow switch operation
_________
_________
j. Microcomputer (if supplied) components dry
_________
_________
Piping:
a. Piping complies with applicable codes
_________
_________
b. External piping independently supported
_________
_________
c. Chilled water lines insulated
_________
_________
d. All systems refrigerant and water piping leak tested and corrected as
_________
_________
necessary
Before Start-Up:
a. Open compressor discharge service valve (if supplied)
_________
_________
b. Open liquid valve(s)
_________
_________
c. Open suction, and discharge valves to pressure gauges (if supplied)
_________
_________
d. Check rotation of all fan motors
_________
_________
e. Start auxiliary equipment (pumps, fans, etc.)
_________
_________
f. Is crankcase heater operating? Operate 24 hours prior to
unit start-up.
_________
_________
g. Check the compressor oil level through the crankcase sight glass.
_________
_________
The oil level should be 1/2 of the glass. If the level is low, add
_________
_________
oil in accordance with the directions in the maintenance instructions
_________
_________
h. Check all control settings as specified on unit wiring diagram
_________
_________
i. Air purged from chilled water system
_________
_________
After Start-up:
a. Check high pressure control
_________
_________
b. Check oil temperature safety switch
_________
_________
c. Check and adjust low temperature freeze control
_________
_________
d. Check and adjust unit controller
_________
_________
e. Check and adjust low pressure control
_________
_________
f. Check and adjust expansion valve superheat
_________
_________
31