background image

A formula for calculating ramp time in minutes is
T = [(# compressors x 100) - start pt.] x Compressor
Control Interval/(Ramp rate x 60)]

The compressor control interval can be determined by
timing the frequency of load/unload pulses given to a
compressor. It is typically 2 seconds.

4.5.  Manual Lead/Lag Selection

The lead compressor can be selected by the lead
B setpoint. The number stored in this setpoint
should be one less than the desired compressor
number. So a 0.0 in the setpoint specifies com-
pressor 1 as the lead, a 1.0 puts compressor 2 as
lead, etc. It is preferable to have compressor 1 as
the lead. If a compressor is locked off, the next
compressor will automatically take its place in the
lead/lag sequence.

4.6.  Compressor Start Delay

A compressor start delay of one or two minutes is
incorporated into the computer to prevent two
compressors from starting at the same time and
insure that the system load requires another com-
pressor. The compressor control point will display
COFF (“clock off”) during this timing.

4.7

Power Loss Reset
This function allows the customer the option of
automatic or manual reset of the computer after
a power loss to the computer.  The power loss
could be from the UVR or control switch.  For au-
tomatic reset, a 0.0 is stored in the power in the
power loss B setpoint.  For manual reset after
power failure, a 1.0 is stored in the set- point.  A
power loss alarm is also recorded by the computer.

4.8. Anti-Recycle Timing

At the start of a compressor, a 15 minute timer is
initiated during which the compressor cannot start.
If cooling is called for during this time, a COFF is
displayed in the compressor control point.

CAUTION

: This timer is bypassed by manual

control of compressors. 

DO NOT 

manually start

a compressor more than once every 15 minutes.

For an air-cooled unit, the time delay is two min-
utes when ambient temperature is above 40°F. If
ambient temperature drops below 40°F, the delay
on compressor start up is extended to 4 minutes.
After start-up, the low pressure delay is 2 min-
utes.

4.10 High Pressure Safety

If the condensing pressure of a refrigeration circuit
exceeds the high pressure A setpoint, all compres-

4.9.  Low Pressure Safety

When the evaporator pressure of a given refrig-
eration circuit drops below the low pressure B
setpoint, a time delay is initiated. If the pressure
stays below the setpoint during the time period,
all compressors on the circuit will be locked off
and the low pressure alarm will be recorded by
the computer.

4.11 Freeze Safety

If the leaving water temperature of a chiller drops

below the freeze B setpoint, all of the compressors
will be locked off. The freeze alarm will be recorded
by the computer. Press RESET to clear the lockout.

4.12 High Oil Temp Safety

If the oil temperature switch of a compressor opens,

the oil temperature digital input turns ON. If the
compressor is operating, the compressor will be
locked off. The high oil temperature alarm will be
recorded by the computer and RESET must be pressed
after the problem is resolved.

4.13 Alarm Output

The alarm control point closes the digital output

relay on all safety alarms. This relay is used to turn
an alarm light on.  After the problem is resolved,
press RESET to reset the system and turn the alarm
output off.

4.14 Fan Control

The fans are controlled by the microcomputer out
put relays. The computer switches fans on or off
basel on the discharge pressure and the fan
pressure setpoints. The high (A) setpoints are
where the fans turn on and the low (B) setpoints

are where the fans turn off.

4.15 Chilled Water Reset (Optional) and Customer Con-

trol Interlock

If an analog input is available, the chilled water tem-

perature setpoint can be raised automatically by a
0-5 VDC signal provided by an external controller.
The reset signal must be between 0VDC and 5VDC,
with 0VDC being no reset and 5VDC being maxi-
mum reset. The maximum temperature reset (in-
crease) desired must be stored in CWR max B
setpoint. For example, to raise the chilled water
setpoint from 44°F to 50°F (6.0°F) with a 5VDC in-
put, a 6.0 is stored in CWR max setpoint.

sors on the circuit are locked off.  The high pressure
alarm will be recorded by the computer.  Typical
setpoint value is 360 psig.

CAUTION:

  The voltage input must never exceed

5.0VDC.

Control contacts from an external controller are
used to enable or disable operation of compres-
sors. The wiring diagram specifies the terminals to
which the contacts must be wired.  To enable the
compressors, the contacts must be closed. To
place the unit in stand-by mode, open the control
contact.

Note

: This control must be used for automatic

control of the package. Do not use the flow
switch to control the package.

15

Summary of Contents for HRSC - D

Page 1: ...loading System 7 Control Settings 8 9 Sequence of Operation 9 10 Optional Microcomputer Controller 10 thru 16 Electrical Data 60 Hz 17 18 Typical Power Wiring 19 Typical Control Wiring Electro Mechani...

Page 2: ...control system If the package is installed operated and maintained with care and attention to the instructions contained herein it will give many years of satisfactory service It is assumed the user...

Page 3: ...30 LOCATION CLEARANCE Location of the equipment and the size of the equipment room require careful consideration of the following factors 1 Route by which the chiller will be moved within the build i...

Page 4: ...ld be followed for multiple unit application NOTE A constant chilled water flow rate is assumed to be maintained through all coolers Parallel Chilled Water Flow Units Method A Both units operate simul...

Page 5: ...TYPICAL CHILLED WATER PIPING TYPICAL MULTIPLE PACKAGED CHILLER WATER CONNECTIONS 4 PARALLEL FLOW PARALLEL FLOW SERIES FLOW...

Page 6: ...practices for re frigeration systems Use small screw unit start up report Form NS1157 to record all temperature pressure electrical readings and control set tings A copy must be forwarded to Dunham Bu...

Page 7: ...holding tank must be clean and free of any mois ture Evacuate tank to 200 microns The holding tank can be a receiver or reclaiming tank of a size large enough for the total oil change and must be abl...

Page 8: ...supply water temperature The slide valve will move to the left loading by force of discharge pressure whenever UL 1 opens to permit flow to SLIDE VALVE UNLOADING SYSTEM the oil return low pressure li...

Page 9: ...scharge Temperature OS 4 Compressor Solid State Module CSTM 5 Low Water Temperature T2 6 Phase Loss Monitor PLM 7 Control Circuit Breaker CB1 If any of these devices should open due to abnormal condit...

Page 10: ...coming Power Terminal Block Warning DO NOT REVERSE THE LEADS ON THE PHASE LOSS MONITOR FOR THIS WILL ALLOW THE COMPRESSORS TO RUN BACKWARDS CAUSING SEVERE DAMAGE AND WILL VOID THE COMPRESSOR WARRANTY...

Page 11: ...r This motor starter is then held in by C1 N O auxiliary contacts After five seconds TD9 N O contacts close de energizing Star contactor S1 and energizing run contactor C2 through S1 N O auxiliary con...

Page 12: ...clear was performed This records up to 65 000 cycles C CURRENT TARGET VALUE VALUE VALUE VALUE The values under CURRENT and TARGET give different operating analog input values and setpoints for differ...

Page 13: ...NTER to continue The last ENTER will store the new date and time WARNING Setting the clock will cause a system reset The entire unit will shut down and start over again If the change was started inadv...

Page 14: ...of each of the functions follows 4 1 Capacity Control of Screw Compressors The capacity of a compressor can be controlled manually or automatically The status of a compressor can be observed by displa...

Page 15: ...lly it can be com manded to load hold or unload If current limit is active it will not accept a load command CAUTION Anti recycle timer is bypassed by NOTE All compressors will revert back to auto mat...

Page 16: ...cuit drops below the low pressure B setpoint a time delay is initiated If the pressure stays below the setpoint during the time period all compressors on the circuit will be locked off and the low pre...

Page 17: ...indi cates a loose wire blown fuse defective sensor or faulty analog board 4 19 External Shutdown Indication No Run Alarm A No Run control point error is generated if the computer tries to start or ru...

Page 18: ...08 230 Y D 205 179 409 347 436 600 460 XL 91 74 485 422 188 250 460 Y D 91 74 162 141 188 250 208 230 XL 205 205 1228 1228 462 600 120 208 230 Y D 205 205 409 409 462 600 460 XL 91 91 485 485 205 250...

Page 19: ...1415 1415 1415 1415 471 462 600 600 208 230 XL 209 209 209 209 472 472 472 472 471 462 600 600 460 Y D 98 98 98 98 539 539 539 539 403 500 460 XL 98 98 98 98 180 180 180 180 403 500 208 230 Y D 209 2...

Page 20: ...19 TYPICAL HRSC 150 POWER WIRING 460 3 60 COMPRESSOR MOTORS 1 2 SEE NOTE 5...

Page 21: ...20 TYPICAL HRSC 150 CONTROL WIRING Electrical Mechanical...

Page 22: ...21 TYPICAL HRSC 150 CONTROL WIRING Optional Micro Computer Controller...

Page 23: ......

Page 24: ...3 CIRC 180 210 225 4 CIRC 240 255 270 300 CAP t HOT GAS REGULATOR SOLENOID VALVE HOT GAS BYPASS OPTION CIRC 1 ONLY TACCESS VALVE COUPL ING ACCESS VALVE CHECK COUPLING VALVE DISCHA RG E RFW Sum comp SC...

Page 25: ...1 SPD SD Condenser Size 70 70 70 140 140 140 140 140 Refrigerant Charge R22 lbs 1 96 130 156 208 228 247 280 312 HRSC Operating Weight lbs 2 1700 2100 2325 3240 3555 4590 5415 5910 SEMI HERMETIC SCRE...

Page 26: ...220 225 EXT18122J07DFRO 7 270 1060 240 255 270 300 EXT20122J07DFRO 8 300 1140 These chillers have welded heads All other chillers have removable heads NOTE Constant water flow through the evaporator i...

Page 27: ...OUT SPREADER BAR ISOLATOR ASSEMBLY FRONT VIEW CONTROL BOX MIDPOINT UNIT ISOLATOR OPTIONAL UNIT FRAME RAIL SHIPPED LOOSE WITH ISOLATOR OPTION ONLY 18 1 13 3 8 ISOLATOR CROSS RAIL 6 1 1 2 3 3 2 9 3 4 DI...

Page 28: ...HOLES HOLES 6 SUPPLIED ISOLATOR MOUNTING 2 1 2 DIA LIFTING HOLES 4 BY OTHERS CONDENSER BUMPER RAIL 6 3 4 DIA HOLES SUPPLIED FILTER DRIER COMPRESSOR COMPRESSOR 2 2 75 3 1 2 75 12 1 2 CONTROL BOX END 1...

Page 29: ......

Page 30: ......

Page 31: ...Check water flow thru cooler and correct as required COMPRESSOR CYCLES ON HIGH PRESSURE CONTROL 1 Compressor discharge valve partially closed 1 Open valve fully 2 Non condensible gases in system 2 Ope...

Page 32: ...k tested and corrected as _________ _________ necessary Before Start Up a Open compressor discharge service valve if supplied _________ _________ b Open liquid valve s _________ _________ c Open sucti...

Reviews: