background image

GENERAL

Packaged chillers are designed to cool water or other non-
corrosive liquids. Water is circulated through the direct ex-
pansion cooler where it is cooled to the desired temperature
then circulated to cooling coils for air conditioning, or to
other types of heat exchangers for process cooling.

Care should be taken to see that the equipment is properly
installed and adjusted. An installer or operator should first
become familiar with the information contained in this
manual.

INSPECTION

When the equipment is delivered, it is important that the fol-
lowing inspection be completed in the presence of the carrier’s
representative.

1. Check all crates and cartons received against the Bill of

Lading/Shipping Papers to be sure they agree.

2. Check the model number and the electrical characteristics

on the nameplate to determine if they are correct.

3. Check for freight damage, shortages or other discrepan

cies and note them on the delivery receipt before
signing.

In the event that any damage is found, a damage claim should
immediately be filed by the purchaser against the delivering
carrier as all shipments are F.O.B. Factory.

STORAGE

The HRSC unit is designed for indoor use and should be
stored indoors and/or protected from the elements.

RIGGING

General 

- Each unit has been carefully tested and crafted at

the factory where every precaution is taken to assure that
the unit reaches you in perfect condition.  It is very important
that the riggers and movers should use the same care and
precaution in moving the equipment into place. Make sure
that chains, cables, or other moving equipment are placed
so as to avoid damage to the unit or piping. The refrigerant
piping must not be used as a ladder or as a hand hold.  Do
not attach a chain hoist sling to the piping or equipment.
Move the unit in an upright position and let it down gently
from trucks or rollers.

Rigging and Moving 

- Any unit mounted on skids may be

moved with a forklift, but care must be taken not to damage
the unit with forks. The skids should not be removed until
the unit is at its final location.

The HRSC units are to be rigged thru the holes in the base
side rails. 

In all cases, spreader bars

 must be used between

rigging lines to prevent damage.  The unit must be lifted
using 

All Rigging Point

s.  Refer to Rigging Instructions on

pages 29 & 30.

LOCATION & CLEARANCE

Location of the equipment and the size of the equipment
room require careful consideration of the following factors:

1. Route by which the chiller will be moved within the build

ing to the equipment room. Make sure there are adequate
clearance and floor strength through doors and passage
ways.

2. Space required for final connections and for normal equip-

ment maintenance. Sufficient clearance should be allowed,
between unit and walls, to permit cleaning or repair of
cooler tubes.

3. Effect of location on piping sizes and piping layout.
4. Location of service facilities; power supply, water and
    approved drainage.
5. Motor starting restrictions of local power company.

Another consideration which must be taken into account is
that the unit should be mounted away from noise sensitive
spaces and must have adequate support to avoid vibration
and noise transmission into the building. Units should be
mounted over corridors, utility areas, rest rooms or other
auxiliary areas where sound levels are not an important fac-
tor. Sound and structural consultants should be retained for
recommendations on critical installations.

FOUNDATION

A flat concrete foundation or floor, which can support the
weight of the equipment, must be provided. The unit must
be level for proper operation and functioning of controls.

VIBRATION ISOLATION

Under certain critical conditions, it may be necessary to in-
stall vibration isolators under the base of the Packaged Chiller.

Rubber-in-shear or spring vibration isolators are offered as
optional items. When spring isolators are used, flexible con-
nections must be installed in the water piping system and in
the refrigerant lines of split systems. Note: These flexible con-
nectors must be suitable for the fluid and pressures involved.

All piping which is external to the packaged chiller must be
supported by spring mounted hangers and any piping which
goes through the wall, ceiling or floor should be properly
sheathed to prevent transmission of piping vibration to the
structure.

When spring isolators are used, electrical service to the unit
must also be flexibly connected, by means of a 36" section of
flexible conduit.

PIPING CONNECTIONS

Water Connections, Chilled Water Piping

 - After the unit

has been leveled, the external water piping may be made
up. Be sure water piping is connected to the correct fittings.
The water out connection is closest to the expansion valve
(R-in) end. A chilled water flow switch must be installed in
the external chilled water outlet piping.

2

Summary of Contents for HRSC - D

Page 1: ...loading System 7 Control Settings 8 9 Sequence of Operation 9 10 Optional Microcomputer Controller 10 thru 16 Electrical Data 60 Hz 17 18 Typical Power Wiring 19 Typical Control Wiring Electro Mechani...

Page 2: ...control system If the package is installed operated and maintained with care and attention to the instructions contained herein it will give many years of satisfactory service It is assumed the user...

Page 3: ...30 LOCATION CLEARANCE Location of the equipment and the size of the equipment room require careful consideration of the following factors 1 Route by which the chiller will be moved within the build i...

Page 4: ...ld be followed for multiple unit application NOTE A constant chilled water flow rate is assumed to be maintained through all coolers Parallel Chilled Water Flow Units Method A Both units operate simul...

Page 5: ...TYPICAL CHILLED WATER PIPING TYPICAL MULTIPLE PACKAGED CHILLER WATER CONNECTIONS 4 PARALLEL FLOW PARALLEL FLOW SERIES FLOW...

Page 6: ...practices for re frigeration systems Use small screw unit start up report Form NS1157 to record all temperature pressure electrical readings and control set tings A copy must be forwarded to Dunham Bu...

Page 7: ...holding tank must be clean and free of any mois ture Evacuate tank to 200 microns The holding tank can be a receiver or reclaiming tank of a size large enough for the total oil change and must be abl...

Page 8: ...supply water temperature The slide valve will move to the left loading by force of discharge pressure whenever UL 1 opens to permit flow to SLIDE VALVE UNLOADING SYSTEM the oil return low pressure li...

Page 9: ...scharge Temperature OS 4 Compressor Solid State Module CSTM 5 Low Water Temperature T2 6 Phase Loss Monitor PLM 7 Control Circuit Breaker CB1 If any of these devices should open due to abnormal condit...

Page 10: ...coming Power Terminal Block Warning DO NOT REVERSE THE LEADS ON THE PHASE LOSS MONITOR FOR THIS WILL ALLOW THE COMPRESSORS TO RUN BACKWARDS CAUSING SEVERE DAMAGE AND WILL VOID THE COMPRESSOR WARRANTY...

Page 11: ...r This motor starter is then held in by C1 N O auxiliary contacts After five seconds TD9 N O contacts close de energizing Star contactor S1 and energizing run contactor C2 through S1 N O auxiliary con...

Page 12: ...clear was performed This records up to 65 000 cycles C CURRENT TARGET VALUE VALUE VALUE VALUE The values under CURRENT and TARGET give different operating analog input values and setpoints for differ...

Page 13: ...NTER to continue The last ENTER will store the new date and time WARNING Setting the clock will cause a system reset The entire unit will shut down and start over again If the change was started inadv...

Page 14: ...of each of the functions follows 4 1 Capacity Control of Screw Compressors The capacity of a compressor can be controlled manually or automatically The status of a compressor can be observed by displa...

Page 15: ...lly it can be com manded to load hold or unload If current limit is active it will not accept a load command CAUTION Anti recycle timer is bypassed by NOTE All compressors will revert back to auto mat...

Page 16: ...cuit drops below the low pressure B setpoint a time delay is initiated If the pressure stays below the setpoint during the time period all compressors on the circuit will be locked off and the low pre...

Page 17: ...indi cates a loose wire blown fuse defective sensor or faulty analog board 4 19 External Shutdown Indication No Run Alarm A No Run control point error is generated if the computer tries to start or ru...

Page 18: ...08 230 Y D 205 179 409 347 436 600 460 XL 91 74 485 422 188 250 460 Y D 91 74 162 141 188 250 208 230 XL 205 205 1228 1228 462 600 120 208 230 Y D 205 205 409 409 462 600 460 XL 91 91 485 485 205 250...

Page 19: ...1415 1415 1415 1415 471 462 600 600 208 230 XL 209 209 209 209 472 472 472 472 471 462 600 600 460 Y D 98 98 98 98 539 539 539 539 403 500 460 XL 98 98 98 98 180 180 180 180 403 500 208 230 Y D 209 2...

Page 20: ...19 TYPICAL HRSC 150 POWER WIRING 460 3 60 COMPRESSOR MOTORS 1 2 SEE NOTE 5...

Page 21: ...20 TYPICAL HRSC 150 CONTROL WIRING Electrical Mechanical...

Page 22: ...21 TYPICAL HRSC 150 CONTROL WIRING Optional Micro Computer Controller...

Page 23: ......

Page 24: ...3 CIRC 180 210 225 4 CIRC 240 255 270 300 CAP t HOT GAS REGULATOR SOLENOID VALVE HOT GAS BYPASS OPTION CIRC 1 ONLY TACCESS VALVE COUPL ING ACCESS VALVE CHECK COUPLING VALVE DISCHA RG E RFW Sum comp SC...

Page 25: ...1 SPD SD Condenser Size 70 70 70 140 140 140 140 140 Refrigerant Charge R22 lbs 1 96 130 156 208 228 247 280 312 HRSC Operating Weight lbs 2 1700 2100 2325 3240 3555 4590 5415 5910 SEMI HERMETIC SCRE...

Page 26: ...220 225 EXT18122J07DFRO 7 270 1060 240 255 270 300 EXT20122J07DFRO 8 300 1140 These chillers have welded heads All other chillers have removable heads NOTE Constant water flow through the evaporator i...

Page 27: ...OUT SPREADER BAR ISOLATOR ASSEMBLY FRONT VIEW CONTROL BOX MIDPOINT UNIT ISOLATOR OPTIONAL UNIT FRAME RAIL SHIPPED LOOSE WITH ISOLATOR OPTION ONLY 18 1 13 3 8 ISOLATOR CROSS RAIL 6 1 1 2 3 3 2 9 3 4 DI...

Page 28: ...HOLES HOLES 6 SUPPLIED ISOLATOR MOUNTING 2 1 2 DIA LIFTING HOLES 4 BY OTHERS CONDENSER BUMPER RAIL 6 3 4 DIA HOLES SUPPLIED FILTER DRIER COMPRESSOR COMPRESSOR 2 2 75 3 1 2 75 12 1 2 CONTROL BOX END 1...

Page 29: ......

Page 30: ......

Page 31: ...Check water flow thru cooler and correct as required COMPRESSOR CYCLES ON HIGH PRESSURE CONTROL 1 Compressor discharge valve partially closed 1 Open valve fully 2 Non condensible gases in system 2 Ope...

Page 32: ...k tested and corrected as _________ _________ necessary Before Start Up a Open compressor discharge service valve if supplied _________ _________ b Open liquid valve s _________ _________ c Open sucti...

Reviews: