background image

4.16  Hot Gas Bypass Control (option)

When hot gas bypass has been supplied with
the package, an output from the computer
controls the solenoid. The solenoid is turned on
if only one compressor is operating and the
target percent capacity of the compressor
drops below the hot gas bypass B setpoint. If
the target percent capacity then climbs above
the hot gas bypass A setpoint, the solenoid is
turned off. Typical setpoints are 45% for the B
setpoint and 80% for the A setpoint.

4.17 Compressor Power Control (No-Stop Alarm) and

Unit Schedule
The control power/schedule feeds power to the
compressor safety and control circuit and closes
the chilled water pump contacts.  (See Field
Control Wiring). After power-up, the relay is
held open for 15 seconds to allow for reset of
the high temperature safety switch. The relay is
then closed to allow normal compressor control
if the unit schedule is calling for unit operation.

The computer will open this relay if it detects
that a compressor auxiliary contact digital input
stays ON for 15 seconds when the computer is
commanding the compressor to be off. A No-
Stop alarm would then be stored in the alarm
history. This would indicate that either a hard-
ware problem is forcing the compressor to run
when it should not or that the digital input is
staying on when the compressor is actually off.
When the problem is resolved, press the RESET
button to allow the machine to start.

During normal operation, this output turns ON/
OFF based on the unit schedule of operation
(see Section 3.9).

4.18 Sensor Alarm Shutdown

If the computer measures an analog sensor
value that is outside of a given boundary, the
associated compressors are shutdown.  The
computer then stores the alarm code corres-
ponding to the sensor alarm.  The boundary
values are as follows:

  Low

  High

1. Water temp sensor

  -

190°F

2. Air temp. sensor

25°F

180°F

3. Suction pressure

-20 psig

See below

4. Discharge pressure

5 psig

   -

The high setpoint for the suction pressure sensor will
be triggered if the leaving water temperature is less
than 60°F and suction pressure is greater than 150
psig.

If one of these sensor alarms occurs, it usually indi-
cates a loose wire, blown fuse, defective sensor, or
faulty analog board.

4.19 External Shutdown Indication (No-Run Alarm)

A No-Run control point error is generated if the
computer tries to start (or run) a compressor but  the
compressor is held off by an external control.       The
computer determines that the compressor is

16

not operating if the associated digital input
from the compressor contactor does not
indicate that the contactor is pulled in (digital
input stays OFF), or if the amps of the com-
pressor are less than about 12 amps.  If a
faulty No-run alarm occurs, monitor the digital
input and amps to see which is producing the
fault.

4.20 Fast Unload Solenoid Control

When a compressor starts, it’s fast unload
solenoid is energized for 30 seconds to ensure
that the compressor unloads fully. The load
and unload, solenoids are de-energized during
this time delay. After the time delay, normal
control of the load/unload solenoids is re-
stored.

4.21 Low Suction/Discharge Differential Alarm

If the difference between suction and dis
charge pressure is less than minimum differen-
tial pressure for 3 minutes while a compressor
is operating, all the compressors on the
affected refrigerant circuit are locked off. A
low differential pressure alarm will be recorded
by the computer and the alarm output will be
turned on. Press RESET to clear the lockout.

4.22  High Motor Temperature Safety

If the high motor temperature switch of a
compressor opens, the motor temperature
digital input turns ON. If the compressor is
operating, the ‘compressor will be locked off.
The high motor temperature alarm will be
recorded by the computer and RESET must be
pressed after the problem is resolved.

4.23 Low Chiller Flow Alarm

A low flow alarm will be generated if a com-
pressor control point is ON and the flow
switch digital input is OFF. All compressors will
be locked off and the alarm light turned on.
After resolving the problem, press RESET.

4.24 High Discharge Pressure Unload

This function unloads the compressor if
discharge pressure is approaching the high
pressure limit. If discharge pressure of an
operating compressor reaches the high
pressure setpoint minus 10 psi, the compressor
will be prevented from loading (HOLD state). If
the discharge pressure reaches the high
pressure setpoint minus 5 psi, the compressor
will begin unloading.

Summary of Contents for HRSC - D

Page 1: ...loading System 7 Control Settings 8 9 Sequence of Operation 9 10 Optional Microcomputer Controller 10 thru 16 Electrical Data 60 Hz 17 18 Typical Power Wiring 19 Typical Control Wiring Electro Mechani...

Page 2: ...control system If the package is installed operated and maintained with care and attention to the instructions contained herein it will give many years of satisfactory service It is assumed the user...

Page 3: ...30 LOCATION CLEARANCE Location of the equipment and the size of the equipment room require careful consideration of the following factors 1 Route by which the chiller will be moved within the build i...

Page 4: ...ld be followed for multiple unit application NOTE A constant chilled water flow rate is assumed to be maintained through all coolers Parallel Chilled Water Flow Units Method A Both units operate simul...

Page 5: ...TYPICAL CHILLED WATER PIPING TYPICAL MULTIPLE PACKAGED CHILLER WATER CONNECTIONS 4 PARALLEL FLOW PARALLEL FLOW SERIES FLOW...

Page 6: ...practices for re frigeration systems Use small screw unit start up report Form NS1157 to record all temperature pressure electrical readings and control set tings A copy must be forwarded to Dunham Bu...

Page 7: ...holding tank must be clean and free of any mois ture Evacuate tank to 200 microns The holding tank can be a receiver or reclaiming tank of a size large enough for the total oil change and must be abl...

Page 8: ...supply water temperature The slide valve will move to the left loading by force of discharge pressure whenever UL 1 opens to permit flow to SLIDE VALVE UNLOADING SYSTEM the oil return low pressure li...

Page 9: ...scharge Temperature OS 4 Compressor Solid State Module CSTM 5 Low Water Temperature T2 6 Phase Loss Monitor PLM 7 Control Circuit Breaker CB1 If any of these devices should open due to abnormal condit...

Page 10: ...coming Power Terminal Block Warning DO NOT REVERSE THE LEADS ON THE PHASE LOSS MONITOR FOR THIS WILL ALLOW THE COMPRESSORS TO RUN BACKWARDS CAUSING SEVERE DAMAGE AND WILL VOID THE COMPRESSOR WARRANTY...

Page 11: ...r This motor starter is then held in by C1 N O auxiliary contacts After five seconds TD9 N O contacts close de energizing Star contactor S1 and energizing run contactor C2 through S1 N O auxiliary con...

Page 12: ...clear was performed This records up to 65 000 cycles C CURRENT TARGET VALUE VALUE VALUE VALUE The values under CURRENT and TARGET give different operating analog input values and setpoints for differ...

Page 13: ...NTER to continue The last ENTER will store the new date and time WARNING Setting the clock will cause a system reset The entire unit will shut down and start over again If the change was started inadv...

Page 14: ...of each of the functions follows 4 1 Capacity Control of Screw Compressors The capacity of a compressor can be controlled manually or automatically The status of a compressor can be observed by displa...

Page 15: ...lly it can be com manded to load hold or unload If current limit is active it will not accept a load command CAUTION Anti recycle timer is bypassed by NOTE All compressors will revert back to auto mat...

Page 16: ...cuit drops below the low pressure B setpoint a time delay is initiated If the pressure stays below the setpoint during the time period all compressors on the circuit will be locked off and the low pre...

Page 17: ...indi cates a loose wire blown fuse defective sensor or faulty analog board 4 19 External Shutdown Indication No Run Alarm A No Run control point error is generated if the computer tries to start or ru...

Page 18: ...08 230 Y D 205 179 409 347 436 600 460 XL 91 74 485 422 188 250 460 Y D 91 74 162 141 188 250 208 230 XL 205 205 1228 1228 462 600 120 208 230 Y D 205 205 409 409 462 600 460 XL 91 91 485 485 205 250...

Page 19: ...1415 1415 1415 1415 471 462 600 600 208 230 XL 209 209 209 209 472 472 472 472 471 462 600 600 460 Y D 98 98 98 98 539 539 539 539 403 500 460 XL 98 98 98 98 180 180 180 180 403 500 208 230 Y D 209 2...

Page 20: ...19 TYPICAL HRSC 150 POWER WIRING 460 3 60 COMPRESSOR MOTORS 1 2 SEE NOTE 5...

Page 21: ...20 TYPICAL HRSC 150 CONTROL WIRING Electrical Mechanical...

Page 22: ...21 TYPICAL HRSC 150 CONTROL WIRING Optional Micro Computer Controller...

Page 23: ......

Page 24: ...3 CIRC 180 210 225 4 CIRC 240 255 270 300 CAP t HOT GAS REGULATOR SOLENOID VALVE HOT GAS BYPASS OPTION CIRC 1 ONLY TACCESS VALVE COUPL ING ACCESS VALVE CHECK COUPLING VALVE DISCHA RG E RFW Sum comp SC...

Page 25: ...1 SPD SD Condenser Size 70 70 70 140 140 140 140 140 Refrigerant Charge R22 lbs 1 96 130 156 208 228 247 280 312 HRSC Operating Weight lbs 2 1700 2100 2325 3240 3555 4590 5415 5910 SEMI HERMETIC SCRE...

Page 26: ...220 225 EXT18122J07DFRO 7 270 1060 240 255 270 300 EXT20122J07DFRO 8 300 1140 These chillers have welded heads All other chillers have removable heads NOTE Constant water flow through the evaporator i...

Page 27: ...OUT SPREADER BAR ISOLATOR ASSEMBLY FRONT VIEW CONTROL BOX MIDPOINT UNIT ISOLATOR OPTIONAL UNIT FRAME RAIL SHIPPED LOOSE WITH ISOLATOR OPTION ONLY 18 1 13 3 8 ISOLATOR CROSS RAIL 6 1 1 2 3 3 2 9 3 4 DI...

Page 28: ...HOLES HOLES 6 SUPPLIED ISOLATOR MOUNTING 2 1 2 DIA LIFTING HOLES 4 BY OTHERS CONDENSER BUMPER RAIL 6 3 4 DIA HOLES SUPPLIED FILTER DRIER COMPRESSOR COMPRESSOR 2 2 75 3 1 2 75 12 1 2 CONTROL BOX END 1...

Page 29: ......

Page 30: ......

Page 31: ...Check water flow thru cooler and correct as required COMPRESSOR CYCLES ON HIGH PRESSURE CONTROL 1 Compressor discharge valve partially closed 1 Open valve fully 2 Non condensible gases in system 2 Ope...

Page 32: ...k tested and corrected as _________ _________ necessary Before Start Up a Open compressor discharge service valve if supplied _________ _________ b Open liquid valve s _________ _________ c Open sucti...

Reviews: