background image

Stage 2 Loading

Subsequent to the start of Compressor No.1 an approximate
five minute time delay is incorporated into the microcom-
puter. After this time delay, and a further call for cooling, the
second step of the staging thermostat (T1) will close. This
will energize relay (R2) and time delay (TD2). If all the safety
controls and switches are closed, (see “Safety Control’ sec-
tion for more details) the control circuit for compressor No.2
will energize, allowing the compressor to start. Power is sup-
plied to condenser fan interlock terminal CT20 and CT2 to
enable the remote condenser fan circuit. Relay (R6) will ener-
gize, allowing the liquid line solenoid valve (SOL2) to ener-
gize. Relay (R6) will energize the safety controls the same as
compressor No.1 circuit.

Time delay (TD2) will provide a 30 second jumper around
the low pressure control (LP2) and will energize the full un-
load solenoid (UL3-2) for 30 seconds then energize relay (R4).
Upon energizing relay (R6), the crankcase heater (CCH2) is
de-energized and the normally open contacts of relay (R4)
are closed, allowing the thermostat (T1) to energize the load
solenoid (UL2-1) and the unload solenoid (UL2-2) upon de-
mand. Relays (R1) and (R2) will interlock the water pump
starters.

SHUTDOWN SEQUENCE

Stage 2 Shutdown

After both compressors have unloaded fully and the leaving
water temperature is still lower than the set-point, the sec-
ond step of the thermostat (T1) will open and de-energize
relay (R2), providing an approximate five minute time delay,
again integral with the microcomputer to the start of Com-
pressor No.2. This will close the liquid line solenoid (SOL2)
condenser fan control contactor and turn off Compressor
No.2. Compressor No.1 will load and unload as required.
Compressor No. 2 will not be able to restart for five minutes
due to integral time delays.

Stage 1 Shutdown

If the leaving water temperature is still lower than the set-
point, the first step of the thermostat (T1) will open and de-
energize relay (R1). This will close the liquid line solenoid
(SOL1) condenser fan control contactor and turn off Com-
pressor No.1 as long as it has run for approximately three
minutes. Compressor No.1 will not be able to restart for five
minutes.

STAR-DELTA STARTING

OPEN TRANSITION

Time delay relay (TD1) closes, energizing start contactor (S1)
and the five second transition timer (TD9). Contactor (S1)
closes, tying the center legs of the motor windings together
into the “Star” (wye) configuration. (S1) N.O. auxiliary con-
tacts close and energize motor starter (C1), starting the com-
pressor motor. This motor starter is then “held in” by (C1)
N.O. auxiliary contacts.

After five seconds (TD9) N.O. contacts close, de-energizing
“Star’ contactor (S1) and energizing run contactor C2 through
(S1) N.O. auxiliary contacts. The compressor motor now runs
in the “Delta” configuration.

There is an instant of time (the “open transition”) between
the opening of (S1) power contacts and the closing of (C2)
power contacts, in which power across the motor windings
is interrupted.

MICROCOMPUTER CONTROLLER

1.  General Description

Your Dunham-Bush HRSC is controlled by an NC25 micro-
computer system. The computer system is composed of a
main microcomputer board, several types of input/output (I/
O) boards, and sensors. The I/O boards are connected to the
microcomputer by ribbon cables. These hardware compo-
nents are controlled by the software program in the micro-
computer. The software determines the state of the output
relays based on the input values.

There are two types of inputs to the computer system. A
digital input indicates whether or not voltage is present at
the input. This could be used to determine whether or not a
contactor is pulled in, a water flow switch is made, or the
status of other on/off devices. Another type of input is an
analog input. An analog value is one that varies continu-
ously, such as temperature, pressure, current, etc. An ana-
log input must be converted to a digital value with an ana-
log to digital (A/D) converter board before the computer can
process the data.

The computer system outputs are relays that switch the 115
VAC control devices such as contactors and solenoids.

The software for the computer is stored in three different
types of computer memory chips. The two EPROM chips

(Electrically Programmable Read Only Memory) store gen-
eral operating procedures (algorithms) and are the same for
all packages. The EAROM chip (Electrically Alterable Read
Only Memory) stores the program that defines the logic for a
particular unit. This software is called the data base. Both of
these chips retain their content when power is removed. The
third type of memory is battery backed RAM (Random Ac-
cess Memory) and is used for temporary storage.

Information can be retrieved from the NC25 and displayed
on a video display terminal. The RS232 communications port
is used.  Refer to FORM 6372 for more information.

2.

Microcomputer Hardware Precautions

The following precautions must be taken while work-
ing with the microcomputer system.

2.1 Do not lay the solder side of a computer board on a

metallic surface. This may damage the battery on
the board.

2.2 Cover the computer components completely when

drilling sheet metal near the computer.

2.3 Strip wires away from microcomputer to prevent

strands from falling on components.

10

Summary of Contents for HRSC - D

Page 1: ...loading System 7 Control Settings 8 9 Sequence of Operation 9 10 Optional Microcomputer Controller 10 thru 16 Electrical Data 60 Hz 17 18 Typical Power Wiring 19 Typical Control Wiring Electro Mechani...

Page 2: ...control system If the package is installed operated and maintained with care and attention to the instructions contained herein it will give many years of satisfactory service It is assumed the user...

Page 3: ...30 LOCATION CLEARANCE Location of the equipment and the size of the equipment room require careful consideration of the following factors 1 Route by which the chiller will be moved within the build i...

Page 4: ...ld be followed for multiple unit application NOTE A constant chilled water flow rate is assumed to be maintained through all coolers Parallel Chilled Water Flow Units Method A Both units operate simul...

Page 5: ...TYPICAL CHILLED WATER PIPING TYPICAL MULTIPLE PACKAGED CHILLER WATER CONNECTIONS 4 PARALLEL FLOW PARALLEL FLOW SERIES FLOW...

Page 6: ...practices for re frigeration systems Use small screw unit start up report Form NS1157 to record all temperature pressure electrical readings and control set tings A copy must be forwarded to Dunham Bu...

Page 7: ...holding tank must be clean and free of any mois ture Evacuate tank to 200 microns The holding tank can be a receiver or reclaiming tank of a size large enough for the total oil change and must be abl...

Page 8: ...supply water temperature The slide valve will move to the left loading by force of discharge pressure whenever UL 1 opens to permit flow to SLIDE VALVE UNLOADING SYSTEM the oil return low pressure li...

Page 9: ...scharge Temperature OS 4 Compressor Solid State Module CSTM 5 Low Water Temperature T2 6 Phase Loss Monitor PLM 7 Control Circuit Breaker CB1 If any of these devices should open due to abnormal condit...

Page 10: ...coming Power Terminal Block Warning DO NOT REVERSE THE LEADS ON THE PHASE LOSS MONITOR FOR THIS WILL ALLOW THE COMPRESSORS TO RUN BACKWARDS CAUSING SEVERE DAMAGE AND WILL VOID THE COMPRESSOR WARRANTY...

Page 11: ...r This motor starter is then held in by C1 N O auxiliary contacts After five seconds TD9 N O contacts close de energizing Star contactor S1 and energizing run contactor C2 through S1 N O auxiliary con...

Page 12: ...clear was performed This records up to 65 000 cycles C CURRENT TARGET VALUE VALUE VALUE VALUE The values under CURRENT and TARGET give different operating analog input values and setpoints for differ...

Page 13: ...NTER to continue The last ENTER will store the new date and time WARNING Setting the clock will cause a system reset The entire unit will shut down and start over again If the change was started inadv...

Page 14: ...of each of the functions follows 4 1 Capacity Control of Screw Compressors The capacity of a compressor can be controlled manually or automatically The status of a compressor can be observed by displa...

Page 15: ...lly it can be com manded to load hold or unload If current limit is active it will not accept a load command CAUTION Anti recycle timer is bypassed by NOTE All compressors will revert back to auto mat...

Page 16: ...cuit drops below the low pressure B setpoint a time delay is initiated If the pressure stays below the setpoint during the time period all compressors on the circuit will be locked off and the low pre...

Page 17: ...indi cates a loose wire blown fuse defective sensor or faulty analog board 4 19 External Shutdown Indication No Run Alarm A No Run control point error is generated if the computer tries to start or ru...

Page 18: ...08 230 Y D 205 179 409 347 436 600 460 XL 91 74 485 422 188 250 460 Y D 91 74 162 141 188 250 208 230 XL 205 205 1228 1228 462 600 120 208 230 Y D 205 205 409 409 462 600 460 XL 91 91 485 485 205 250...

Page 19: ...1415 1415 1415 1415 471 462 600 600 208 230 XL 209 209 209 209 472 472 472 472 471 462 600 600 460 Y D 98 98 98 98 539 539 539 539 403 500 460 XL 98 98 98 98 180 180 180 180 403 500 208 230 Y D 209 2...

Page 20: ...19 TYPICAL HRSC 150 POWER WIRING 460 3 60 COMPRESSOR MOTORS 1 2 SEE NOTE 5...

Page 21: ...20 TYPICAL HRSC 150 CONTROL WIRING Electrical Mechanical...

Page 22: ...21 TYPICAL HRSC 150 CONTROL WIRING Optional Micro Computer Controller...

Page 23: ......

Page 24: ...3 CIRC 180 210 225 4 CIRC 240 255 270 300 CAP t HOT GAS REGULATOR SOLENOID VALVE HOT GAS BYPASS OPTION CIRC 1 ONLY TACCESS VALVE COUPL ING ACCESS VALVE CHECK COUPLING VALVE DISCHA RG E RFW Sum comp SC...

Page 25: ...1 SPD SD Condenser Size 70 70 70 140 140 140 140 140 Refrigerant Charge R22 lbs 1 96 130 156 208 228 247 280 312 HRSC Operating Weight lbs 2 1700 2100 2325 3240 3555 4590 5415 5910 SEMI HERMETIC SCRE...

Page 26: ...220 225 EXT18122J07DFRO 7 270 1060 240 255 270 300 EXT20122J07DFRO 8 300 1140 These chillers have welded heads All other chillers have removable heads NOTE Constant water flow through the evaporator i...

Page 27: ...OUT SPREADER BAR ISOLATOR ASSEMBLY FRONT VIEW CONTROL BOX MIDPOINT UNIT ISOLATOR OPTIONAL UNIT FRAME RAIL SHIPPED LOOSE WITH ISOLATOR OPTION ONLY 18 1 13 3 8 ISOLATOR CROSS RAIL 6 1 1 2 3 3 2 9 3 4 DI...

Page 28: ...HOLES HOLES 6 SUPPLIED ISOLATOR MOUNTING 2 1 2 DIA LIFTING HOLES 4 BY OTHERS CONDENSER BUMPER RAIL 6 3 4 DIA HOLES SUPPLIED FILTER DRIER COMPRESSOR COMPRESSOR 2 2 75 3 1 2 75 12 1 2 CONTROL BOX END 1...

Page 29: ......

Page 30: ......

Page 31: ...Check water flow thru cooler and correct as required COMPRESSOR CYCLES ON HIGH PRESSURE CONTROL 1 Compressor discharge valve partially closed 1 Open valve fully 2 Non condensible gases in system 2 Ope...

Page 32: ...k tested and corrected as _________ _________ necessary Before Start Up a Open compressor discharge service valve if supplied _________ _________ b Open liquid valve s _________ _________ c Open sucti...

Reviews: