background image

not have to be earlier than the turn off time.
Schedules turn on by time and day, but turn off
by time alone.

For example, a schedule from

1900 to 0700 Saturdays would turn on at 7:00 PM
Saturday (time and day) and turn off at 7:00 AM
Sunday (time only).

Example: If a unit is to operate at all times except
between the hours of 1:00 AM and 6:00 AM, the
following schedule would be entered:

CP 17 SCHEDULE GRP:1 SCH:1 0600 0100
DAYS: *** ALL DAYS ***

Another example: A typical building may require
cooling from 6:00 AM to 7:00 PM Monday - Friday
and from 7:00 AM - 3:00 PM on Saturdays. The
schedules would be entered as follows:

CP 17 SCHEDULE GRP:1 SCH:1 0600 1900
DAYS:  MTWRF
CP 17 SCHEDULE GRP:1 SCH:2 0700 1500
DAYS: A

4.

HRSC Package Control

In order to start a unit, the following conditions must
be met:
--

chilled water pump running

--

chilled water flow switch made

--

customer control contact closed

--

control switch and compressor switch on

--

main unit power on

--

all safety conditions satisfied

--

reset pressed on microcomputer keypad

--

the compressor has not started within the last 15
minutes

--

leaving chilled water temperature 20°F or more
above set point

The NC25 computer system performs the following
functions on small screw compressor packages:
  1. Capacity control of compressors
  2. Staging of compressors
  3. Compressor current limiting
  4. Ramp control
  5. Manual lead/lag
  6. Compressor start delay
  7. Power loss reset
  8. Anti-recycle timing
  9. Low pressure safety
10. High pressure safety
11. Freeze safety
12. High Oil Temp Safety
13. Alarm output
14. Fan control
15. Customer control interlock
16. Hot Gas Bypass option control
17. Compressor power control (No-stop alarm)
18. Sensor alarm shutdown
19. External shutdown indication (No-run alarm)
20. Fast Unload Solenoid Control (HRSC 50 thru 225)
21. Low suction / discharge differential pressure alarm
22. High Motor temperature safety
23. Low chiller flow alarm

13

A description of each of the functions follows:

4.1. Capacity Control of Screw Compressors

The capacity of a compressor can be controlled
manually or automatically.

The status of a compressor can be observed by
displaying the compressor control point (1/CP, 4/CP,
7/CP or 10/CP). One of the following messages will
be displayed where # is 1, 4, 7 or 10 for compres-
sors 1, 2, 3 or 4:

CP# COMP LOAD COM

Computer load

CP# COMP CURRENT STATUS: LOAD

Manual load

CP# COMP HOLD COM

Computer hold

CP# COMP CURRENT STATUS: HOLD

Manual hold

CP# COMP UNLD COM

Computer
unload

CP# COMP CURRENT STATUS: UNLD

Manual unload

CP# COMP OFF COM

Off on a normal
control shutdown

CP# COMP COFF COM

Off on timer
(clock off)

CP# COMP LOFF MAN

Manual off or
safety shutdown

4.1.1 Automatic Control

The computer calculates the operating per-
cent capacity of a compressor by measuring
discharge pressure and amps. This operating
percent capacity is then compared to a tar-
get percent capacity. If the operating
capacity is outside of a + 3% deadband, the
load or unload solenoids are pulsed to
match the operating and target percent
capacities. Since all compressors have
the same target, their percent capacities are
balanced.

The target percent capacity is given a fixed
value when a compressor starts or stops.
This value is then increased or decreased
based on how far the leaving water tem-
perature (TLW) is from setpoint and also on
how fast the TLW is approaching setpoint.
The target percent capacity will not change
if the temperature is within a temperature
deadband around the setpoint.

Some packages may have logic that prevents
loading if the leaving water temperature is
falling (negative derivative) at a certain rate.

The desired leaving water temperature is
typically stored in setpoint 1 A.

Calibrations of Amps Calculation at Full Load
The amps calculation is calibrated at the
factory and does not normally need to be
altered.  If a compressor is replaced or
improper operation is observed, the amps
values can be calibrated as follows:

1. Check calibration of discharge pressure,

and amps. NOTE: Calibrate amps with
potentiometer on filter board.

Summary of Contents for HRSC - D

Page 1: ...loading System 7 Control Settings 8 9 Sequence of Operation 9 10 Optional Microcomputer Controller 10 thru 16 Electrical Data 60 Hz 17 18 Typical Power Wiring 19 Typical Control Wiring Electro Mechani...

Page 2: ...control system If the package is installed operated and maintained with care and attention to the instructions contained herein it will give many years of satisfactory service It is assumed the user...

Page 3: ...30 LOCATION CLEARANCE Location of the equipment and the size of the equipment room require careful consideration of the following factors 1 Route by which the chiller will be moved within the build i...

Page 4: ...ld be followed for multiple unit application NOTE A constant chilled water flow rate is assumed to be maintained through all coolers Parallel Chilled Water Flow Units Method A Both units operate simul...

Page 5: ...TYPICAL CHILLED WATER PIPING TYPICAL MULTIPLE PACKAGED CHILLER WATER CONNECTIONS 4 PARALLEL FLOW PARALLEL FLOW SERIES FLOW...

Page 6: ...practices for re frigeration systems Use small screw unit start up report Form NS1157 to record all temperature pressure electrical readings and control set tings A copy must be forwarded to Dunham Bu...

Page 7: ...holding tank must be clean and free of any mois ture Evacuate tank to 200 microns The holding tank can be a receiver or reclaiming tank of a size large enough for the total oil change and must be abl...

Page 8: ...supply water temperature The slide valve will move to the left loading by force of discharge pressure whenever UL 1 opens to permit flow to SLIDE VALVE UNLOADING SYSTEM the oil return low pressure li...

Page 9: ...scharge Temperature OS 4 Compressor Solid State Module CSTM 5 Low Water Temperature T2 6 Phase Loss Monitor PLM 7 Control Circuit Breaker CB1 If any of these devices should open due to abnormal condit...

Page 10: ...coming Power Terminal Block Warning DO NOT REVERSE THE LEADS ON THE PHASE LOSS MONITOR FOR THIS WILL ALLOW THE COMPRESSORS TO RUN BACKWARDS CAUSING SEVERE DAMAGE AND WILL VOID THE COMPRESSOR WARRANTY...

Page 11: ...r This motor starter is then held in by C1 N O auxiliary contacts After five seconds TD9 N O contacts close de energizing Star contactor S1 and energizing run contactor C2 through S1 N O auxiliary con...

Page 12: ...clear was performed This records up to 65 000 cycles C CURRENT TARGET VALUE VALUE VALUE VALUE The values under CURRENT and TARGET give different operating analog input values and setpoints for differ...

Page 13: ...NTER to continue The last ENTER will store the new date and time WARNING Setting the clock will cause a system reset The entire unit will shut down and start over again If the change was started inadv...

Page 14: ...of each of the functions follows 4 1 Capacity Control of Screw Compressors The capacity of a compressor can be controlled manually or automatically The status of a compressor can be observed by displa...

Page 15: ...lly it can be com manded to load hold or unload If current limit is active it will not accept a load command CAUTION Anti recycle timer is bypassed by NOTE All compressors will revert back to auto mat...

Page 16: ...cuit drops below the low pressure B setpoint a time delay is initiated If the pressure stays below the setpoint during the time period all compressors on the circuit will be locked off and the low pre...

Page 17: ...indi cates a loose wire blown fuse defective sensor or faulty analog board 4 19 External Shutdown Indication No Run Alarm A No Run control point error is generated if the computer tries to start or ru...

Page 18: ...08 230 Y D 205 179 409 347 436 600 460 XL 91 74 485 422 188 250 460 Y D 91 74 162 141 188 250 208 230 XL 205 205 1228 1228 462 600 120 208 230 Y D 205 205 409 409 462 600 460 XL 91 91 485 485 205 250...

Page 19: ...1415 1415 1415 1415 471 462 600 600 208 230 XL 209 209 209 209 472 472 472 472 471 462 600 600 460 Y D 98 98 98 98 539 539 539 539 403 500 460 XL 98 98 98 98 180 180 180 180 403 500 208 230 Y D 209 2...

Page 20: ...19 TYPICAL HRSC 150 POWER WIRING 460 3 60 COMPRESSOR MOTORS 1 2 SEE NOTE 5...

Page 21: ...20 TYPICAL HRSC 150 CONTROL WIRING Electrical Mechanical...

Page 22: ...21 TYPICAL HRSC 150 CONTROL WIRING Optional Micro Computer Controller...

Page 23: ......

Page 24: ...3 CIRC 180 210 225 4 CIRC 240 255 270 300 CAP t HOT GAS REGULATOR SOLENOID VALVE HOT GAS BYPASS OPTION CIRC 1 ONLY TACCESS VALVE COUPL ING ACCESS VALVE CHECK COUPLING VALVE DISCHA RG E RFW Sum comp SC...

Page 25: ...1 SPD SD Condenser Size 70 70 70 140 140 140 140 140 Refrigerant Charge R22 lbs 1 96 130 156 208 228 247 280 312 HRSC Operating Weight lbs 2 1700 2100 2325 3240 3555 4590 5415 5910 SEMI HERMETIC SCRE...

Page 26: ...220 225 EXT18122J07DFRO 7 270 1060 240 255 270 300 EXT20122J07DFRO 8 300 1140 These chillers have welded heads All other chillers have removable heads NOTE Constant water flow through the evaporator i...

Page 27: ...OUT SPREADER BAR ISOLATOR ASSEMBLY FRONT VIEW CONTROL BOX MIDPOINT UNIT ISOLATOR OPTIONAL UNIT FRAME RAIL SHIPPED LOOSE WITH ISOLATOR OPTION ONLY 18 1 13 3 8 ISOLATOR CROSS RAIL 6 1 1 2 3 3 2 9 3 4 DI...

Page 28: ...HOLES HOLES 6 SUPPLIED ISOLATOR MOUNTING 2 1 2 DIA LIFTING HOLES 4 BY OTHERS CONDENSER BUMPER RAIL 6 3 4 DIA HOLES SUPPLIED FILTER DRIER COMPRESSOR COMPRESSOR 2 2 75 3 1 2 75 12 1 2 CONTROL BOX END 1...

Page 29: ......

Page 30: ......

Page 31: ...Check water flow thru cooler and correct as required COMPRESSOR CYCLES ON HIGH PRESSURE CONTROL 1 Compressor discharge valve partially closed 1 Open valve fully 2 Non condensible gases in system 2 Ope...

Page 32: ...k tested and corrected as _________ _________ necessary Before Start Up a Open compressor discharge service valve if supplied _________ _________ b Open liquid valve s _________ _________ c Open sucti...

Reviews: