14 ... 20
FRM
Edition 10.15
270 440
Function
Sectional drawing SSD
Device in the closed position
1
Valve disc
2
Closing spring
3
Ball catch / trigger mechanism
4
Chamber with the pressure to be monitored
5
Working diaphragm
6
Push rod
7
Setpoint spring for pd
o
8
Setpoint spring for pd
u
9
Protective cap
Chamber 4 is connected to the outlet pressure via
an impulse line. The pressure being monitored
acts on the working diaphragm 5. The force of the
setpoint springs 7 and 8 acts as counterforce. In
case of an unbalance of forces (overpressure or
underpressure), the SSD is actuated and the gas
supply is blocked.