9 ... 20
FRM
Edition 10.15
270 440
The response pressure results
from the force of the installed
adjusting spring and the weight
force of the movable parts. By
changing the setpoint spring
1,
it is possible to set different outlet
pressures.
Selection of regulator springs
Specific set range, outlet pressure W
ds
Spring colour
Order
number
Wire diameter
[mm]
Length
[mm]
Diameter
[mm]
Setpoint range [mbar]
ND
MD
HD
Silver
270341
5.5
220
60
30-40
90-110
Green
270345
6.5
220
62
40-55
110-170
Yellow
270346
7.0
220
63
55-80
170-240
Blue
270347
8.0
220
65
50-100
240-330
Black
270348
9.0
220
68
330-420
400-580
Purple
270349
10.0
220
69
560-850
Orange
270350
11.0
220
71
800-1200
Pink
270352
12.0
220
73
1100-1500
1
←
Table of contents
Summary of Contents for FRM 100025 HD
Page 76: ...32 64 Edition 10 15 Nr 270 047 X Y R Q T S U V W H M C A B D E G F J I K L N O P...
Page 98: ...54 64 Edition 10 15 Nr 270 047 B C I K L M 15 Ersatzteile A D E F G H I J...
Page 140: ...32 64 Edition 10 15 No 270 442 X Y R Q T S U V W H M C A B D E G F J I K L N O P...
Page 162: ...54 64 Edition 10 15 No 270 442 B C I K L M 15 Spare parts A D E F G H I J...
Page 173: ......
Page 174: ......