9. Installation
9.1 General information
•
This device can only be installed in
compliance with the rules and stand
ards applicable and in accordance with
the local regulations and authorisa -
tions that may be necessary.
•
Install the device in a building or
housing, do not install it outdoors without suitable
protective measures!
•
The work area must be provided with general safety
devices.
•
The lifting devices used must be suitable for the load
to be lifted.
•
Enough installation space for operation and mainte
-
nance has to be provided.
•
It is recommended to install a filter with a pore size ≤
50 µm upstream of the regulator.
•
The installation must not impair the functioning of
other components.
Check prior to installation!
•
Shut-off valves both on the inlet and outlet side are
closed.
•
Lines are free from combustible gas.
•
Prevent explosive gas-air mixture: the room atmosphere
must constantly be monitored through gas concentration
measuring devices for the detection of gas leakages.
•
Ensure electrically conductive bridging. Prevent contact
voltage and ignitable flashover.
•
The performance data on the type plate correspond to the
ordering data.
•
Flanges on the inlet side and outlet side of the connecting
line are parallel.
•
The sealing surfaces of the flange are undamaged and
clean.
•
The maximum inlet pressure of the system is lower than
the maximum admissible pressure of the regulator.
•
Protective caps at the connection flange, if any, must be
removed.
•
The minimum distances for the setting must be observed.
•
The pipeline on the inlet side must be free of water and
dirt.
Note during installation!
•
Mounting must be carried out in a tension-free state.
•
Tighten the screws crosswise.
•
Tightening torques must be observed.
•
Vent lines and blow-off lines have to be positioned indi
-
vidually.
•
Vent lines and blow-off lines must lead outdoors: gases
must be able to escape to a non-hazardous environment.
•
The pulse lines may not be shut off.
•
The specified distance between the measuring points of
the pulse lines must be observed.
•
The flow direction (arrow) on the housing must be fol
-
lowed.
Summary of Contents for FRM 100025 HD
Page 76: ...32 64 Edition 10 15 Nr 270 047 X Y R Q T S U V W H M C A B D E G F J I K L N O P...
Page 98: ...54 64 Edition 10 15 Nr 270 047 B C I K L M 15 Ersatzteile A D E F G H I J...
Page 140: ...32 64 Edition 10 15 No 270 442 X Y R Q T S U V W H M C A B D E G F J I K L N O P...
Page 162: ...54 64 Edition 10 15 No 270 442 B C I K L M 15 Spare parts A D E F G H I J...
Page 173: ......
Page 174: ......