4 …64
Edition 10.15 • No
. 270 442
5 … 64
6. Features
6.1. Technical data
Technical data
FRM …
Device
Spring-loaded medium pressure regulator according to EN 334
Type
IS
Type of gas
Family 1+2+3
Nominal diameters
Flange
Connecting flanges PN 25 according to EN 1092-1
DN
25 40 50
Admissible pressure load
10 bar (1000 kPa)
Max. inlet pressure
10 bar (1000 kPa)
Outlet pressure range
30 - 1500 mbar (3-150 kPa)
Minimum differential pressure
(ND)
270 mbar (27 kPa)
Minimum differential pressure
(MD)
350 mbar (35 kPa)
Minimum differential pressure
(HD)
500 mbar (50 kPa)
Materials
Firing valve housing:
cast iron GGG 50
Diaphragm housing:
steel sheet
Diaphragms:
NBR
Ambient temperature
-20 °C to + 60 °C
Technical data
SSD …
Device
Safety shutoff valve in compliance with EN14382, class A
Type
IS
Response time
≤ 2s
Adjustment range
below W
du
10 - 2500 mbar (1-250 kPa)
Adjustment range
above W
du
40 - 4000 mbar (4-400 kPa)
Materials
Firing valve housing:
cast iron GGG 50
Diaphragm housing:
Aluminium
Diaphragms:
NBR
Summary of Contents for FRM 100025 HD
Page 76: ...32 64 Edition 10 15 Nr 270 047 X Y R Q T S U V W H M C A B D E G F J I K L N O P...
Page 98: ...54 64 Edition 10 15 Nr 270 047 B C I K L M 15 Ersatzteile A D E F G H I J...
Page 140: ...32 64 Edition 10 15 No 270 442 X Y R Q T S U V W H M C A B D E G F J I K L N O P...
Page 162: ...54 64 Edition 10 15 No 270 442 B C I K L M 15 Spare parts A D E F G H I J...
Page 173: ......
Page 174: ......