10 ... 20
FRM
Edition 10.15
270 440
The response pressure results from
the force of the installed adjusting
spring. The upper response pres-
sure (overpressure) is set on the
external
spring 1
of the measure-
ment device. The lower response
pressure (vacuum)
can be set on
the internal
spring 2
. By changing
the setpoint springs, different
response pressures
can be set.
Selection of SSD springs
Specific set range, underpressure W
dsu
Spring colour Order number Wire diameter [mm] Length [mm] Diameter [mm]
Setpoint range [mbar]
ND
MD
HD
White
270353
1.2
60
10.0
10-32
Yellow
270355
1.5
55
12.3
24-40
Blue
270356
2.0
55
12.3
30-115
35-110
Black
270357
2.3
55
12.3
50-250
Purple
270358
2.5
55
12.3
80-400
150-500
Orange
270359
2.8
55
12.3
300-1000
Pink
270360
3.0
55
12.5
800-2500
Specific set range, overpressure W
dso
Spring colour Order number Wire diameter [mm] Length [mm] Diameter [mm]
Setpoint range [mbar]
ND
MD
HD
Silver
270361
2.2
60
30.0
40-130
Green
270366
2.5
60
30.0
60-190
180-290
Red
270367
2.7
60
30.0
90-240
230-370
Yellow
270368
3.2
60
30.0
300-500
Blue
270369
3.5
60
30.0
400-800
500-1000
Black
270370
3.7
60
30.0
700-1300
Purple
270371
4.0
60
30.0
1000-1800
Orange
270372
4.5
60
30.0
1300-2500
Pink
270373
4.8
60
30.0
1800-4000
1
2
←
Table of contents
Summary of Contents for FRM 100025 HD
Page 76: ...32 64 Edition 10 15 Nr 270 047 X Y R Q T S U V W H M C A B D E G F J I K L N O P...
Page 98: ...54 64 Edition 10 15 Nr 270 047 B C I K L M 15 Ersatzteile A D E F G H I J...
Page 140: ...32 64 Edition 10 15 No 270 442 X Y R Q T S U V W H M C A B D E G F J I K L N O P...
Page 162: ...54 64 Edition 10 15 No 270 442 B C I K L M 15 Spare parts A D E F G H I J...
Page 173: ......
Page 174: ......