14.2 Maintenance instructions of the regulator
14.2.1 Preparation
1
Loosen the screws
G
(M10) using an open-ended
wrench
SW 17
.
2
Loosen the loops using an open-ended wrench
SW 17
.
2
14.2.2 Replacement of the working diaphragm
4. Unscrew the sealing cap
C
from the spring dome
using a jointed hook wrench
90-155
.
5. Remove the spring washer
D
incl. ball and the
setpoint spring E
.
1. Loosen the pulse imline and the vent line and
remove them.
2. Remove the protective cap
A
.
3. Completely release the setpoint spring at the
adjusting screw
B
using an open-ended wrench
SW 24
.
(–)
1
G
C
E
D
A