9.2 Installation instructions
•
The installation must be carried according to the installa
-
tion scheme specified below.
•
Install the safety shutoff valve in the flow direction (arrow/
housing).
•
Design a straight calming section with the equal diameter.
•
Make sure that the pulse tap at the calming section is
clean and free from burrs. Distance > 5 x DN
•
Maximum flow velocity in the calming section: ≤ 30 m/s.
Pos.
Designation
1
Shutoff valve, inlet side (e.g. ball valve or butterfly valve)
2
Filter
3
Welded part
4
Pressure gauge, inlet side
5
Regulator with integrated SSD
6
Calming section
7
SBV
8
Ball valve
9
Pressure gauge, outlet side
10
Test burner
11
Venting ball valve
12
Pulse line, SSD
13
Pulse line, regulator
14
Shutoff valve, outlet side (e.g. ball valve or butterfly valve)
15
Vent line regulator
16
Vent line SSD
17
Relief line SBV
•
Version of the pulse lines: steel pipe D= 12 x 1.5
•
Avoid accumulation of condensate: install the pulse lines
with a gradient
1
2
3
4
5
8
6
7
9
11
10
12
12
Calming section
> 5 x DN
Installation drawing
13
14
15
16
17
Summary of Contents for FRM 100025 HD
Page 76: ...32 64 Edition 10 15 Nr 270 047 X Y R Q T S U V W H M C A B D E G F J I K L N O P...
Page 98: ...54 64 Edition 10 15 Nr 270 047 B C I K L M 15 Ersatzteile A D E F G H I J...
Page 140: ...32 64 Edition 10 15 No 270 442 X Y R Q T S U V W H M C A B D E G F J I K L N O P...
Page 162: ...54 64 Edition 10 15 No 270 442 B C I K L M 15 Spare parts A D E F G H I J...
Page 173: ......
Page 174: ......