Description Of Controls
42
5.3 CONTROL PUSH-BUTTONS
Icon
Description
Stop / Reset
Mode
This button places the module into its
Stop/Reset Mode
. This clears any
alarm conditions for which the triggering criteria have been removed. If the engine
is running and the module is put into Stop mode, the module automatically
instructs the generator to unload (‘
Close Generator’ and
‘
Delayed Load Output
1, 2, 3 & 4
’
become inactive (if used))
. The fuel supply de-energises and the
engine comes to a standstill. Should any form of
remote start signal
be present
while operating in this mode, a start does not occur.
Manual Mode
This button places the module into its
Manual
Mode
. Once in
Manual
Mode
, the module responds to the
Start
button to start the
generator and run it off load.
To place the generator on load, use the
Transfer to Generator
button. The
module automatically instructs the changeover device to place the generator on
load
(‘
Close Generator
’
and ‘
Delayed Load Output 1, 2, 3 & 4
’
becomes active
(if used))
. To place the generator off load, use the
Transfer to Mains
or
Open
Generator
buttons. The module automatically instructs the changeover device
to place the generator off load
(‘
Close Generator
’
and ‘
Delayed Load Output 1,
2, 3 & 4
’
becomes inactive (if used))
. Additional digital inputs can be assigned to
perform these functions.
If the engine is running off-load in
Manual
Mode
and a
remote start signal
becomes present, the module automatically instructs the changeover device to
place the generator on load
(‘
Close Generator
’
and ‘
Delayed Load Output 1, 2, 3
& 4
’
becomes active (if used))
. Upon removal of the
Remote Start Signal
, the
generator remains on load until either selection of the
Stop/Reset Mode
or
Auto Mode
.
For further details, please see section entitled ‘Operation’ elsewhere in this
manual.
Test Mode (DSE7120 MKII Only)
This button places the module into its
Test Mode
. Once in
Test Mode
, the
module responds to the
Start
button to start the generator and run it off load.
Once the set has started, it is automatically be placed on load (‘
Close Generator
’
and ‘
Delayed Load Output 1, 2, 3 & 4
’ become active in order from lowest to
highest (if used)).
For further details, please see section entitled ‘Operation’ elsewhere in this
manual.
Summary of Contents for DSE7110 MKII
Page 34: ...Installation 34 4 2 1 DSE7110 MKII TYPICAL WIRING DIAGRAM 3 PHASE 4 WIRE ...
Page 35: ...Installation 35 4 2 2 DSE7120 MKII TYPICAL WIRING DIAGRAM 3 PHASE 4 WIRE ...
Page 36: ...Installation 36 4 3 ALTERNATE TOPOLOGY WIRING DIAGRAMS 4 3 1 GENERATOR ...
Page 37: ...Installation 37 4 3 2 MAINS DSE7120 MKII ONLY ...