Specification
19
3.11 ADDING AN EXTERNAL SOUNDER
Should an external alarm or indicator be required, this can be achieved by using the DSE
Configuration Suite PC software to configure an auxiliary output for “Audible Alarm”, and by
configuring an auxiliary input for “Alarm Mute” (if required).
The audible alarm output activates and de-activates at the same time as the module’s internal
sounder. The Alarm mute input and internal
Lamp Test / Alarm Mute
button activate ‘in parallel’
with each other. Either signal mutes the internal sounder and audible alarm output.
Example of configuration to achieve external sounder with external alarm mute button:
3.12 ACCUMULATED INSTRUMENTATION
NOTE: When an accumulated instrumentation value exceeds the maximum number as
listed below, it resets and begin counting from zero again.
Engine Hours Run
Maximum 99999 hrs 59 minutes
(Approximately 11yrs 4months)
Accumulated Power
999999 kWh / kVArh / kVAh
The number of logged Engine Hours and Number of Starts can be set/reset using the DSE
Configuration Suite PC software. Depending upon module configuration, this may have been PIN
number locked by your generator supplier