3.8.2.3 FUEL LEVEL SENSOR
Measurement Type
Resistance measurement by measuring voltage across sensor with
a fixed current applied
Arrangement
Differential resistance measurement input
Measurement Current
11mA ±10%
Full Scale
480
Ω
Over Range / Fail
540
Ω
Resolution
1%
Accuracy
+/-2% of full scale resistance (±9.6
Ω
) excluding transducer error
Max Common Mode Voltage
±2V
Display Range
0% - 250% subject to limits of the sensor
3.8.2.4 FLEXIBLE SENSOR
Number
2 when
Fuel Level Sender
is configured as a flexible
Measurement Type
Resistance measurement by measuring voltage across sensor with
a fixed current applied
Arrangement
Differential resistance measurement input
Measurement Current
11mA ±10%
Full Scale
480
Ω
Over Range / Fail
540
Ω
Resolution
1%
Accuracy
+/-2% of full scale resistance (±9.6
Ω
) excluding transducer error
Max Common Mode Voltage
±2V
Display Range
0% - 250%, 0
°
C - 250
°
C (32°F - 482°F) or 0 bar - 17.2 bar (0PSI -
250PSI)subject to limits of the sensor and sensor configuration
3.8.3 CHARGE FAIL INPUT
Minimum Voltage
0V
Maximum Voltage
35V (plant supply)
Resolution
0.2V
Accuracy
± 1% of max measured voltage
Excitation
Active circuit constant power output
Output Power
2.5W nominal at 12V and 24V
Current At 12V
210mA
Current At 24V
105mA
The charge fail input is actually a combined input and output. Whenever the generator is required to
run, the terminal provides excitation current to the charge alternator field winding.
When the charge alternator is correctly charging the battery, the voltage of the terminal is close to
the plant battery supply voltage. In a failed charge situation, the voltage of this terminal is pulled
down to a low voltage. It is this drop in voltage that triggers the
charge failure
alarm. The level at
which this operates and whether this triggers a warning or shutdown alarm is configurable using the
DSE Configuration Suite Software.
Summary of Contents for DSE7110 MKII
Page 34: ...Installation 34 4 2 1 DSE7110 MKII TYPICAL WIRING DIAGRAM 3 PHASE 4 WIRE ...
Page 35: ...Installation 35 4 2 2 DSE7120 MKII TYPICAL WIRING DIAGRAM 3 PHASE 4 WIRE ...
Page 36: ...Installation 36 4 3 ALTERNATE TOPOLOGY WIRING DIAGRAMS 4 3 1 GENERATOR ...
Page 37: ...Installation 37 4 3 2 MAINS DSE7120 MKII ONLY ...