Section 4: Programming Options
CMS Cellular 1 APN
The Access Point Name (APN) determines the cellular net-
work that the communicator will connect to. This information
is available from the network carrier.
Note:
When a SIM card with a custom APN is used, the unit
will not have access to the Internet. DLS and remote flash
can still be done if a valid public APN is programmed.
Default:
Blank
Valid range:
32 characters ASCII
CMS Cellular 1 Domain Name
This information is provided by the central monitoring station
system administrator.
Default:
Blank
Valid range:
32 characters ASCII
CMS Cellular 2 Account Code
Default: 0 Not in valid range
Valid range: 0000000001 to FFFFFFFFFE
The account code is used by the central monitoring station
to distinguish between different transmitters. This account
code is used when transmitting signals to the central mon-
itoring station receiver.
Note:
Programming this section as all 0’s or F’s will cause a
module configuration trouble (yellow LED = 12 flashes).
Note:
A cellular account code is necessary in order for the
iotega to communicate to the central monitoring station (if
cellular communication path is selected).
Default:
0000000000
Valid range:
0000000000 to FFFFFFFFFF
CMS Cellular 2 DNIS
The DNIS is used in addition to the account code to identify
the communicator module at the central monitoring station.
Default:
000000
Valid range:
000000 to 0FFFFF (first digit not used)
CMS Cellular 2 IP Address
Enter the Cellular receiver 2 IP address. This IP address will
be provided by the central monitoring station.
Note:
When a valid address has been entered, Cellular
Receiver 2 is enabled and will communicate events over the
cellular path.
Default:
000.000.000.000
Valid range:
000.000.000.000.to 255.255.255.255
CMS Cellular 2 Remote Port
Enter the cellular receiver 2 IP address. This IP address will
be provided by the central monitoring station.
Note:
When a valid address has been entered, cellular
receiver 2 is enabled and will communicate events over the
cellular path.
Default:
3061 (0BF5)
Valid range:
0000 to 65535
CMS Cellular 2 APN
The APN determines the cellular network that the com-
municator will connect to. This information is available from
the network carrier.
Note:
When a SIM card with a custom APN is used, the unit
will not have access to the Internet. DLS and remote flash
can still be done if this option is programmed with a valid
public APN.
Default:
Blank
Valid range:
32 characters ASCII
CMS Cellular 2 Domain Name
This information is provided by the central monitoring station
system administrator.
Default:
Blank
Valid range:
32 characters ASCII
4.3.1 Other Communicator Related
Options
Alternate Test Transmission
When this option is enabled, the test transmission alternates
between primary and secondary receivers with each test
transmission interval.
When disabled, the test transmission is sent to the pro-
grammed receivers, based on the settings of the periodic
test transmission reporting codes.
Default:
Enabled
Valid range:
Enabled/Disabled