Igniters per fireplace
For each fireplace there is one igniter that is started via
this module and that can be reset following an error.
•
Start:
Switches on the pilot flame.
Stop:
Switches off the pilot flame.
Flashing green: Pilot flame is started.
Lit green: Pilot flame burning
flashing red: New alarm present
Lit red: Acknowledged alarm present
•
Reset:
Reset the igniter after an alarm. The button is only active when there is an
alarm.
•
Failed starts:
Counter for failed starts. After 5 failed starts, the background color
changes from gray to red. Following a purging time of 1 minutes, the alarm can be
acknowledged.
•
Remaining runtime:
Displays the remaining burning duration of the igniter when the
fireplace is not being used and is shown visually underneath in a bar. The igniter is
deactivated automatically after 900 seconds when the fireplace is not activated.
System purging:
Displays the remaining purging time in seconds and visually
underneath in a bar.
Selecting the ignition
The following ignition options can be selected via
the pull-down menu:
•
S
tart igniter via the remote control
•
Start the igniter via the touchpanel
The ignition can only be started via the selected device (remote control or touchscreen).
Fireplace status
Displays the status of the fireplace.
•
Flame level:
Displays the current flame level as a
number and underneath in a blue bar. The flame
level is only displayed when operating the fire pan
fireplace in container 3.
•
Remaining runtime:
Displays the remaining runtime of the fireplace in seconds and
visually underneath in a bar.
Remaining cooling time:
Displays the remaining cooling time in seconds and visually
underneath in a bar.
i
i
NOTICE
Gas can accumulate in closed fire rooms in the area of the fireplace after five subsequent
unsuccessful ignition attempts with the igniter, which can cause uncontrolled combustion.
After 5 failed ignition attempts in succession, the ventilator in C3 is switched to maximum
power for 1 minute to remove any gas residues from the fire room. Afterwards, the alarm
of the igniter can be reset using the reset button on the cabinet or in the software.
Fig. 71 Igniters
Fig. 72 Ignition selection
Fig. 73 Fireplace status