56
3-4-1-4-9-2
Level 1 closed
0
90
99.9
e s Level in the receiver tank at which the supply
valve is closed
3-4-1-4-10-1
Level setpoint 1
0
80
99.9
e s Maximum level in the receiver tank at which the
proportional valve is fully closed
3-4-1-4-10-3
Hysteresis
0
15
99.9
e s Differential level in the receiver tank at which the
proportional valve is fully opened
3-4-1-4-10-4
Sample time
0
10
99
e s Time between the level measurements controlling
the proportional valve position
3-4-3-2
Proportional const.
0
3
100
e s Proportional amplification factor the system pres-
sure is controlled with
3-4-3-3
Integral time
0
0.9
60
e s Speed with which the deviation of the required
system pressure is adjusted
3-4-3-4
Differential time
0
Max 99.99
e s The level of damping with which the deviation of
the required system pressure is controlled
3-4-3-5-1
No flow bandwith
0
6
50
e s Bandwidth of the no flow detection
3-4-3-5-2
No flow time
0
16
600
e s Time of the no flow detection in s
3-4-3-9
VFD Ramp-Up
0.1
3
Max 999
e s Setting of the ramp-up of the VFD
3-4-3-10
VFD Ramp-Down
0.1
3
999
e s Setting of the ramp-down of the VFD
3-4-3-11
VFD min. frequency
0
30
140
e s Minimum frequency of the VFD
3-5-1
Set point
0
400
1000
e c System pressure set point
3-5-3
Bandwidth
0
5
999
e c Bandwidth
3-5-4
Accumulation press.
0
30
999
e c Membrane tank (water) pressure accumulation
prior to the system switch-off
3-5-10
Delta p
-999
0
999
e c Quadratic function to correct the setpoint when a
pump is switching on or off
3-5-11
High pressure alarm
400
1000
e c Upper limit value for the system pressure to shut
down or notification only (signal)
3-5-13
Low pressure alarm
0
400
e c Under limit value for the system pressure to shut
down or notification only (signal)
Parameter
Disp
lay
text
Va
lu
e
1
descrip
tio
n
Min./Max
.
Read
Wr
it
e
Help
text