18
9.2
Hydro-Unit MC ++
ATTENTION
See factory settings 3-2-2-1
When as a result of a increasing water volume the
pressure drops below the pressure set point, a pump
will be switched on. When the required system
pressure has been reached, the pumps are switched
off one at a time. The minimum run time related
switch-off delay is optimized constantly, which results
in a considerable energy saving.
Table 17: Specific parameter settings MC ++
Figure 6: 1 pump operation
Figure 7: 2 pump operation
Figure 8: 3 pump operation
Parameter
Value
3-3-1
Number of pumps
1
2
3
4
5
6
3-3-2
Inlet
Switch
Pressure
Level / valve ON-OFF
Level / valve prop.
3-3-3
Discharge
Fixed Speed
3-5-1
Set point
.... kPa
3-5-3
Bandwidth
50
3-5-13
Low pressure alarm
100 kPa
3-6-1
Opt. pump starts/h
30
3-6-2
Min. run time
1 s
3-6-3
Min. run time cor.
1 s
3-6-8
Run-dry delay
Default 30 s
Float/level control 1 s