57
3-6-2
Min. run time
0
180
999
e c The minimum time of the pump to run. (the run
time correction will not drop below this value)
3-6-5
Start delay
0
1
999
e s Start delay to switch the pumps on when pressure
remains low
3-6-6
Stop delay
0
1
999
e s Stop delay to switch the pumps off when pressure
remains high.
3-6-8
RDP delay
0
10
999
e s Delay time after run-dry protection to shut down
the system
3-6-9
High/low alarm delay
10
60
999
e s Permitted time of setpoint pressure deviation > too
high or too low system pressure.
1.
Bold is Factory setting.
Parameter
Disp
lay
text
Va
lu
e
1
descrip
tio
n
Min./Max
.
Read
Wr
it
e
Help
text