40
3-4-1-4-8-2
Threshold 1 OFF
0
50
199.9
e s Water level at which the relays output becomes
""low""
3-4-1-4-8-3
Threshold 2 ON
0
40
199.9
e s Water level at which the relays output becomes
""high""
3-4-1-4-8-4
Threshold 2 OFF
0
40
199.9
e s Water level at which the relays output becomes
""low""
3-4-1-4-9
Supply valve ON/OFF
e n The supply valve open/closed with which the
receiver tank is filled
3-4-1-4-9-1
Level 1 open
0
70
99.9
e s Level in the receiver tank at which the supply
valve is opened
3-4-1-4-9-2
Level 1 closed
0
90
99.9
e s Level in the receiver tank at which the supply
valve is closed
3-4-1-4-9-3
Level 1A open
0
40
99.9
e s Alternative level (Clock alternated) in the receiver
tank at which the supply valve is opened
3-4-1-4-9-4
Level 1A closed
0
60
99.9
e s Alternative level (Clock alternated) in the receiver
tank at which the supply valve is closed
3-4-1-4-10
Supply valve prop.
e n The supply valve proportional opened with which
the receiver tank is filled
3-4-1-4-10-1
Level setpoint 1
0
80
99.9
e s Maximum level in the receiver tank at which the
proportional valve is fully closed
3-4-1-4-10-2
Level setpoint 1A
0
40
99.9
e s Alternative level (Clock alternated) in the receiver
tank at which the proportional valve is fully closed
3-4-1-4-10-3
Hysteresis
0
15
99.9
e s Differential level in the receiver tank at which the
proportional valve is fully opened
3-4-1-4-10-4
Sample time
0
10
99
e s Time between the level measurements controlling
the proportional valve position
3-4-1-4-10-5
Analog output
4-20 mA
0-20 mA
e s Analog output configuration, 4-20mA / 0-20mA
3-4-1-4-10-6
Open band
0
2
15
e s Band below the setpoints 1 and 1A, at which the
prop. control of the valve is suppressed.
3-4-1-4-11
Water supply control
e s
3-4-1-4-11-1
Level RW-pump Off
70
90
99.9
e s Level in the tank at which the rainwater pump is
switched off.
3-4-1-4-11-2
Level RW-Pumpe On
40
70
90
e s Level in the tank at which the rainwater pump is
switched on and the potable water inlet valve is
closed.
3-4-1-4-11-3
Level DW-valve open
0
40
70
e s Level in the tank at which the potable water inlet
valve is opened.
3-4-1-4-11-4
Overflow protection
OFF
ON
e s Overflow protection to stop any water inlet if digital
input "Leakage" is activated.
Parameter