41
3-4-1-5
Auto. Setpoint Redu.
e n Automatic setpoint reduction by low inlet pressure
3-4-1-5-1
ASR function
OFF
ON
e s Automatic setpoint reduction function
3-4-1-5-2
Switch on point
100
200
400
e s The pumps are switched On, if inlet pressure is
above switch-On point for more then Switch-On
time
3-4-1-5-3
Inlet Set point
100
400
e s Inlet setpoint used for automatic reduction by low
inlet pressure
3-4-1-5-4
Switch off point
0
90
100
e s The pumps are switched off, if inlet pressure is
below switch-off point for more then switch-off
time
3-4-1-5-5
Proportional const.
0
3
10
e s Proportional amplification factor the system pres-
sure is controlled with
3-4-1-5-6
Integral time
0
0.9
60
e s Speed with which the deviation of the required
system pressure is adjusted
3-4-1-5-7
Differential time
0
99.99
e s The level of damping with which the deviation of
the required system pressure is controlled
3-4-1-5-8
ARW delay factor
5/100
d d Setting for ARW control, sampletime factor tarw
>= 5 * ts
3-4-1-5-9
Switch On time
0
5
60
s s Switching on time after Automatic setpoint reduc-
tion shutdown alarm
3-4-1-5-10
Switch Off time
0
5
60
s s Shutdown is not actived if the inlet pressure is not
less then set value for switch-off time
3-4-1-6
Potable water inlet
e s
3-4-1-6-1
Refresh intervall
0
336
999
e s Time duration between two potable water refresh-
ment sequences of the inlet
3-4-1-6-2
Force refresh
OFF
ON
e s Forced potable water refrehment of the inlet also if
water level in tank is higher than level B.
3-4-1-6-3
Refresh duration
0
10
300
e s Time duration for potable water refreshment of the
inlet
3-4-1-7
Rainwater inlet
e s
3-4-1-7-1
Number of pumps
1
2
e s Number of rainwater pumps
3-4-1-7-2
Max. pumpstarts
1
30
60
e s Maximum allowed starts per hour of rainwater
pump
3-4-1-7-3
Max. run time
0
1800
3600
e s Maximum continuous run time of the rainwater
pump. After this time the rainwater pump will be
forced to change over.
3-4-1-7-4
Check run interval
0
172800
2592000
e s The interval time between the check runs applica-
ble for rain water pumps not operating.
3-4-1-7-5
Check run duration
0
2
60
e s The check-run time per pump.
3-4-2
Discharge
e s Discharge pressure settings
Parameter
Disp
lay
text
Va
lu
e
1
descrip
tio
n
Min./Max
.
Read
Wr
it
e
Help
text