20
9.4
Hydro-Unit MCF
ATTENTION
See factory settings 3-2-2-1
The Hydro-Unit MCF is equipped with one variable
frequency drive. If the Hydro-Unit is rotation-
controlled, the required system pressure is sensed by
a pressure sensor on the outlet side of the
installation. An integrated adjustable PID-controller in
the software of the Megacontrol ensures that the
system pressure remains constant by successively
switching on or off one or more (whether or not)
rotation-controlled pumps with delay. A pump is only
switched on when 100% or respectively 0% of the
speed has been reached.
Table 19: Specific parameter settings MCF
Figure 12: 1 pump operation, 1 pump variable
Figure 13: 2 pump operation, 1 pump variable
Figure 14: 3 pump operation, 1 pump variable
Parameter
Value
3-3-1
Number of pumps
1
2
3
4
5
6
3-3-2
Inlet
Switch
Pressure
Level / valve ON-OFF
Level / valve prop.
3-3-3
Discharge
VFD change-over
3-4-3-1
Communication
Analog 0-20 mA /
4-20 mA
3-4-3-2
Proportional const.
3
3-4-3-3
Integral const.
0.9
3-5-1
Set point
.... kPa
3-5-3
Bandwidth
10
3-5-4
Accumulation press.
30 kPa
3-5-13
Low pressure alarm
100 kPa
3-6-1
Opt. pump starts/h
30
3-6-2
Min. run time
1 s
3-6-3
Min. run time corr.
0 s
3-6-8
Run-dry delay
Default 30 s
Float/level control 1 s