21
9.5
Hydro-Unit MCMF
ATTENTION
See factory settings 3-2-2-1
The Hydro-Unit MCMF is equipped with multiple
variable frequency drives. If the Hydro-Unit is
rotation-controlled, the required system pressure is
sensed by a pressure sensor on the outlet side of the
installation. An integrated adjustable PID-controller in
the software of the Megacontrol ensures that the
system pressure remains constant by successively
switching on or off one or more (whether or not)
rotation-controlled pumps with delay. A pump is only
switched on when 100% or respectively 0% of the
speed has been reached.
Table 20: Specific parameter settings MCMF
9.6
Hydro-Unit PumpDrive 2 Eco
ATTENTION
See factory settings 3-2-2-1
Figure 15: 1 pump operation, 1 pump variable
Figure 16: 2 pump operation, 2 pump variable
Figure 17: 3 pump operation, 3 pump variable
Parameter
Value
3-3-1
Number of pumps
1
2
3
4
5
6
3-3-2
Inlet
Switch
Pressure
Level / valve ON-OFF
Level / valve prop.
3-3-3
Discharge
VFD fixed all
3-4-3-1
Communication
Danfoss VLT 2800
Danfoss MicroDrive
Danfoss AquaDrive
3-4-3-2
Proportional const.
3
3-4-3-3
Integral time.
0.9
3-4-3-4
Differential time.
0
3-4-3-5-1 No flow bandwidth
0-1000 kPa
6
0-2500 kPa
16
3-4-3-5-3 No flow step
1
3-4-3-9
VFD Ramp-Up
3
3-4-3-10 VFD Ramp-Down
3
3-4-3-11
VFD min. frequency
30
3-4-3-12 VFD max. frequency
160
3-4-3-13 P nominal of VFD
1500 See VFD
3-4-3-14 U nominal of VFD
400 See VFD
3-4-3-15 F nominal of VFD
50/60
3-4-3-16 I nominal of VFD
4 See VFD
3-4-3-17 RPM nominal of VFD
2880 See motor name
plate
3-5-1
Set point
.... kPa
3-5-3
Bandwidth
10
3-5-4
Accumulation press.
30 kPa
3-5-13
Low pressure alarm
100 kPa
3-6-1
Opt. pump starts/h
30
3-6-2
Min. run time
1 s
3-6-3
Min. run time corr.
0 s
3-6-8
Run-dry delay
Default 30 s
Float/level control 1 s