The Hydro-Unit Megacontrol is equipped with multiple
variable frequency drives. If the Hydro-Unit is
rotation-controlled, the required system pressure is
sensed by a pressure sensor on the outlet side of the
installation. An integrated adjustable PID-controller in
the software of the Megacontrol ensures that the
system pressure remains constant by successively
switching on or off one or more (whether or not)
rotation-controlled pumps with delay. A pump is only
switched on when 100% or respectively 0% of the
speed has been reached.
Table 21: Specific parameter settings Megacontrol
Figure 18: 1 pump operation, 1 pump variable
Figure 19: 2 pump operation, 2 pump variable
Figure 20: 3 pump operation, 3 pump variable
Parameter
Value
3-1-1-3-1 Pressure
kPa
3-3-1
Number of pumps
1
2
3-3-2
Inlet
Switch
3-3-3
Discharge
VFD fixed all
3-4-2-1
Sensor press. 4 mA
See pressure trans-
mitter
3-4-2-2
Sensor press. 20 mA
See pressure trans-
mitter
3-4-2-3
Pumps ON sensor fail
1
3-4-2-4
Max power
Limitation of the maxi-
mum power / maxi-
mum system load (1
pump is 100%)
3-4-3-1
Communication
PumpDrive 2
3-4-3-2
Proportional const.
3
3-4-3-3
Integral time.
0.9
3-4-3-4
Differential time.
0
3-4-3-5-1 No flow bandwidth
0-1000 kPa
6
0-2500 kPa
16
3-4-3-5-2 No flow time
16
3-4-3-5-3 No flow step
3
3-4-3-5-4 No flow max. power
100
3-4-3-9
VFD Ramp-Up
Depends on motor
size
3-4-3-10 VFD Ramp-Down
Depends on motor
size
3-4-3-11
VFD min. frequency
30 Hz
3-4-3-12 VFD max. frequency
50/60 Hz
3-4-3-13 P nominal of VFD
Motorpower W
3-4-3-14 U nominal of VFD
400 V
3-4-3-15 F nominal of VFD
50/60 Hz
3-4-3-16 I nominal of VFD
Imax motor (by correct
Fand U) / Imax VFD
3-4-3-17 RPM nominal of VFD
RPM at the correct F
3-5-1
Set point
400
3-5-3
Bandwidth
With pressure vessel
10 kPa / Without pres-
sure vessel 20 kPa
3-5-4
Accumulation press.
30 kPa
3-5-5
Max.set point
See pressure class
3-5-11
High pressure alarm
See pressure class
3-5-13
Low pressure alarm
100 kPa
3-6-1
Opt. pump starts/h
30
3-6-2
Min. run time
10
3-6-3
Min. run time corr.
0
3-6-8
RDP delay
Default 30 s
Float-level control 1 s