Installation
7.1
Mechanical installation
ATTENTION
Contact the supplier if parts are missing
or damaged.
Build in the control unit using suitable fastening
material. Consult the annex “Built-in diagram" for the
correct overall dimensions.
7.2
Electrical installation
WARNING
Only authorized personnel is allowed to
connect the control unit electrically in
accordance with the local regulations.
Electrical connections
•
Make sure that the electric control unit
specifications correspond with the power supply
to which is connected.
•
Consult the annex "Electrical diagram" for a list
of all electrical power points.
7.2.1
Recommended RS485-termination for
Megacontrol
The new board for Megacontrol is based on a new
hardware platform. One new feature is, that the
clamps for the external RS485-bus (J301) will now
benefit the advantage of galvanic isolated bus- and
GND-lines.
7.2.2
Parameter settings of the frequency
converters
At the configuration VFD fixed all (parameter 3-3-3)
you can set the selected VFD (parameter 3-4-3-1).
Before you can set the VFD you have to disable the
pump by pump in 'Operating mode: off' (parameter 1-
2-1).
By setting the VFD's using the Megacontrol use the
following sequence:
Table 9: Megacontrol parameter
After entering these parameters, the other
parameters can be set at their discretion. Always
check the correct setting of the frequency converters
parameters.
A
RS485-termination with 1…6 “DANFOSS Micro-
Drives”
1
Megacontrol : keep the termination clamps on the
Megacontrol T+ / T- open
2
Microdrives: switch the bus termination to position
on, on each Micro Drive.
B1
RS485-termination with 1…2 “DANFOSS AQUA
Drives”
1
Megacontrol : keep the termination clampson the
Megacontrol T+ / T- open
2
AQUA Drive: switch the bus termination to position
on, on each AQUA Drive
B2
RS485-termination with 3…6 “DANFOSS AQUA
Drives”
1
Megacontrol : keep the termination clamps on the
Megacontrol T+ / T- open
2
AQUA Drive: set the bus termination only on the
last AQUA Drive
3
External termination: Place, near to the Megacon-
trol, an external active bus termination, like nor-
mally used for Profibus, for example: 6ES7 972-
0DA00-0AA0 or FBCon DP M12 Term 24V
No Parameter Description
1
3-4-3-20
Motor speed unit Hz
2
3-4-3-13
P nominal of VFD
3
3-4-3-14
U nominal of VFD
4
3-4-3-15
F nominal of VFD
5
3-4-3-16
I nominal of VFD
6
3-4-3-17
RPM nominal of VFD
7
3-4-3-9
VFD Ramp-Up
8
3-4-3-10
VFD Ramp-Down
9
3-4-3-11
VFD min. frequency
10 3-4-3-12
VFD max. frequency