Doc. #
: M1800, Rev. 06
Page 72 of 101
www.opwglobal.com
DMS Installation
NOTE
: As density sensing is no longer an option in the system, the
sensor itself will be picked up by the system once the device is
installed and after redoing Auto-Detection of the probe.
1. Take the probe out of the tank and remove the clip
and nylon probe foot at the bottom of the probe.
2. Remove the water float, slide the density sensor on
and tighten the screws of the sensor onto the probe
shaft (the umbrella should be facing down). Leave a
space of at least 4 to 6 inches (10.2 cm - 15.2 cm) at
the bottom of the probe shaft to allow the water float
to detect at least 3 inches (7.6 cm) of water.
3. Replace the water float, nylon probe foot and end clip.
4. Place probe back in the tank.
Tank Thresholds
1. As the Density Sensor is installed between the water
and Product Float, the Product Float will not be able
to go further down than the Density Sensor. In order
to provide low-product alarms, the Low and Low-Low
product threshold level should be set above the
Density Sensor. The suggested level is 17 inches
(43.2 cm) or higher.
2. Measure the distance between the end of the probe
shaft and top end of the Density Sensor. To this
distance, add 2 inches (5.1 cm) to account for the
dead zone at the end of the probe. The resulting value
represents the minimum product Low-Low threshold.
Low-Low Threshold
DMS Configuration & Preliminary Calibration
For DMS configuration and calibration please refer to the
“M1801
SiteSentinel
®
Integra™ Configuration Manual.”
Summary of Contents for OPW SiteSentinel Integra 100
Page 18: ...Doc M1800 Rev 06 Page 18 of 101 www opwglobal com 2 7 Field Wiring Diagram for Integra 100 ...
Page 19: ...Doc M1800 Rev 06 Page 19 of 101 www opwglobal com ...
Page 20: ...Doc M1800 Rev 06 Page 20 of 101 www opwglobal com 2 8 Field Wiring Diagram for Integra 500 ...
Page 21: ...Doc M1800 Rev 06 Page 21 of 101 www opwglobal com ...
Page 48: ...Doc M1800 Rev 06 Page 48 of 101 www opwglobal com 10 3 3 Flex Probe Determination Worksheet ...
Page 52: ...Doc M1800 Rev 06 Page 52 of 101 www opwglobal com Figure 11 4 Tighten Sensor ...
Page 83: ...Doc M1800 Rev 06 Page 83 of 101 www opwglobal com Appendix H Model 924B Installation Records ...
Page 86: ...Doc M1800 Rev 06 Page 86 of 101 www opwglobal com L048 Overall Length ...
Page 99: ...Doc M1800 Rev 06 Page 99 of 101 www opwglobal com Appendix M Declaration of Conformity ...
Page 100: ...Doc M1800 Rev 06 Page 100 of 101 www opwglobal com ...