Appendix A: OPW Smart Sensors
Interstitial Level Sensor Float Switch
OPW P/N: 30-0231-S
Interstitial Level Sensors are used primarily in the interstitial area of a
steel double-walled tank. The sensor contains a float switch that
activates in the presence of a liquid. The sensor is constructed from
chemical-resistant non-metallic material. It can also be used in
sumps, dispenser pans and other locations where the presence of a
liquid could indicate that a leak has occurred. In the event of a break
in the cable, the system will activate the alarm.
This technology allows the Integra and I.S. barrier to automatically
detect sensor connection, sensor type and sensor status, will
minimize user entry error and identify hardware issues with minimal
troubleshooting.
Interstitial Level Sensor Float Switch Specifications
Primary Use(s):
Interstitial Area
Alternate Use(s):
Sumps and Dispenser Pans
Detects:
Liquid
Operating Temperature:
-40°F to 168°F (-40°C to +70°C)
Dimensions:
Length: 3.9” (9.9 cm); Diameter: 1.3”
(3.3 cm)
Cable Requirements:
Belden #88760 or Alpha #55371
Maximum Wiring Length*:
1,000’ (305 m) field wiring
Multi-Drop Restriction:
16 per I.S. barrier channel (64 per
barrier)
Connections:
Red = Power, Black = Signal, Shield =
Ground
*NOTE
: Maximum Wiring Length is the maximum length of cable to
be used to connect all sensors on an individual channel. This length
includes run of cable from I.S. Barrier to each sensor board in the
string.
IntelliSense
™
Board
Interstitial Level Sensor
Float Switch
Summary of Contents for OPW SiteSentinel Integra 100
Page 18: ...Doc M1800 Rev 06 Page 18 of 101 www opwglobal com 2 7 Field Wiring Diagram for Integra 100 ...
Page 19: ...Doc M1800 Rev 06 Page 19 of 101 www opwglobal com ...
Page 20: ...Doc M1800 Rev 06 Page 20 of 101 www opwglobal com 2 8 Field Wiring Diagram for Integra 500 ...
Page 21: ...Doc M1800 Rev 06 Page 21 of 101 www opwglobal com ...
Page 48: ...Doc M1800 Rev 06 Page 48 of 101 www opwglobal com 10 3 3 Flex Probe Determination Worksheet ...
Page 52: ...Doc M1800 Rev 06 Page 52 of 101 www opwglobal com Figure 11 4 Tighten Sensor ...
Page 83: ...Doc M1800 Rev 06 Page 83 of 101 www opwglobal com Appendix H Model 924B Installation Records ...
Page 86: ...Doc M1800 Rev 06 Page 86 of 101 www opwglobal com L048 Overall Length ...
Page 99: ...Doc M1800 Rev 06 Page 99 of 101 www opwglobal com Appendix M Declaration of Conformity ...
Page 100: ...Doc M1800 Rev 06 Page 100 of 101 www opwglobal com ...