Hydrocarbon Liquid Sump Sensor
Part #30-3219-12
Hydrocarbon Liquid Sump Sensor
The Hydrocarbon Liquid Sump Sensor is designed to detect the
presence of liquid hydrocarbons in sumps, dispenser pans and other
locations where the presence of a hydrocarbon liquid could indicate
that a leak has occurred.
The Hydrocarbon Liquid Sump Sensor contains a carbon-polymer
material that changes its resistance when exposed to liquid
hydrocarbons. In the event of a break in the cable, the system will
activate the alarm.
Hydrocarbon Liquid Sump Sensor
Substance Detected:
Liquid Hydrocarbon
Operating Temperature:
-4°F to 122°F (-20°C to +50°C)
Dimensions:
1.7” x 31.2” (4.4 cm x 33.5 cm)
Required Cable:
12’ (3.6 m) gas-and-oil resistant cable
Maximum Wiring Length:
1000
’ (305 m)
Nominal resistance
(uncontaminated):
1K - 5K ohms
Nominal resistance
(contaminated):
30K - 200K ohms
Multi-Drop Restriction:
1 per channel
Connections:
Red = Power, Black = Signal
Summary of Contents for OPW SiteSentinel Integra 100
Page 18: ...Doc M1800 Rev 06 Page 18 of 101 www opwglobal com 2 7 Field Wiring Diagram for Integra 100 ...
Page 19: ...Doc M1800 Rev 06 Page 19 of 101 www opwglobal com ...
Page 20: ...Doc M1800 Rev 06 Page 20 of 101 www opwglobal com 2 8 Field Wiring Diagram for Integra 500 ...
Page 21: ...Doc M1800 Rev 06 Page 21 of 101 www opwglobal com ...
Page 48: ...Doc M1800 Rev 06 Page 48 of 101 www opwglobal com 10 3 3 Flex Probe Determination Worksheet ...
Page 52: ...Doc M1800 Rev 06 Page 52 of 101 www opwglobal com Figure 11 4 Tighten Sensor ...
Page 83: ...Doc M1800 Rev 06 Page 83 of 101 www opwglobal com Appendix H Model 924B Installation Records ...
Page 86: ...Doc M1800 Rev 06 Page 86 of 101 www opwglobal com L048 Overall Length ...
Page 99: ...Doc M1800 Rev 06 Page 99 of 101 www opwglobal com Appendix M Declaration of Conformity ...
Page 100: ...Doc M1800 Rev 06 Page 100 of 101 www opwglobal com ...