Doc. #
: M1800, Rev. 06
Page 54 of 101
www.opwglobal.com
12
Sensor
Technology Overview
The OPW smart sensors have the ability to monitor all contained
areas of the fuel-storage system: tank interstice, piping sumps, STP
containment sumps, dispenser sumps/pans and monitoring wells.
Sensors connected to the I.S. barrier are automatically detected and
identified by the console.
12.1.1 OPW Smart Sensors
For specific sensor descriptions and specifications, please see
Appendix A.
•
Interstitial Level Sensor Float Switch
•
Single-Level Sump Sensor
•
Liquid-Only Float Sensor
•
Discriminating Dispenser Pan Sensor
•
Discriminating STP Sump Sensor
•
Hydrocarbon Vapor Sensor
•
Discriminating Interstitial Sensor
•
Interstitial Hydrocarbon Liquid Sensor with Water Indicator
•
Hydrocarbon Liquid Sensor with Water Indicator
•
Dual-Float Dispenser Sump Sensor
•
Dual-Float Brine Sensor
12.2
IntelliSense™ Technology
This technology allows the Integra and I.S. barrier to automatically
detect sensor connection, sensor type and sensor status. IntelliSense
will minimize user entry error and identify hardware issues with
minimal troubleshooting.
12.3 Multi-drop Installation
The Integra’s internal barrier and optional VSmart Module allows for
the ability to multi-drop the sensors and probes. When using this
installation method; follow the below directions to ensure approved
wiring.
NOTE
: Sensors and probes cannot be multi-dropped from the same
I.S. Channel; therefore, you must run sensors and probes to different
channels on the barrier.
NOTE
: Seal packs are required with all wiring applications in the
field. Weatherproof junction boxes are REQUIRED with ALL I.S. field
connections.
Figure 12-1 Multi-drop Sensor on I.S. Barrier
Summary of Contents for OPW SiteSentinel Integra 100
Page 18: ...Doc M1800 Rev 06 Page 18 of 101 www opwglobal com 2 7 Field Wiring Diagram for Integra 100 ...
Page 19: ...Doc M1800 Rev 06 Page 19 of 101 www opwglobal com ...
Page 20: ...Doc M1800 Rev 06 Page 20 of 101 www opwglobal com 2 8 Field Wiring Diagram for Integra 500 ...
Page 21: ...Doc M1800 Rev 06 Page 21 of 101 www opwglobal com ...
Page 48: ...Doc M1800 Rev 06 Page 48 of 101 www opwglobal com 10 3 3 Flex Probe Determination Worksheet ...
Page 52: ...Doc M1800 Rev 06 Page 52 of 101 www opwglobal com Figure 11 4 Tighten Sensor ...
Page 83: ...Doc M1800 Rev 06 Page 83 of 101 www opwglobal com Appendix H Model 924B Installation Records ...
Page 86: ...Doc M1800 Rev 06 Page 86 of 101 www opwglobal com L048 Overall Length ...
Page 99: ...Doc M1800 Rev 06 Page 99 of 101 www opwglobal com Appendix M Declaration of Conformity ...
Page 100: ...Doc M1800 Rev 06 Page 100 of 101 www opwglobal com ...