Input Voltage:
23 - 28 VDC
Probe Length:
Minimum 1
2’ to 70’ in one-inch increments
Enclosure Material:
Kynar®
Rating:
IP68
Resolution:
0.010” (0.25 mm) Inventory Mode
Linearity:
+/- 0.01% of Full Scale
+/-
0.010” (0.25 mm), whichever is greater
Repeatability:
+/- 0.001% of Full Scale
+/-
0.00025” (0.64 mm), whichever is greater
Temp. Accuracy:
Ab/- 2°F (+/- 1°C)
Temp. Measurement:
Up to five (5) along the sensor span;
Resolution: +/- 0.01°F (+/- 0.01°C)
Temp. Sensing:
-40°F to +158°F (-40°C to +70°C)
Operating Temp.:
-40°F to +158°F (-40°C to +70°C)
Environment:
NEMA 4-rated
Floats (not included):
Specs based on 4” (10.2 cm) standard floats
Listings:
UL; Intrinsically Safe
I.S. Barrier:
24V; OPW P/N: 20-4345
Multi-Drop Capability:
Requires one I.S. Barrier channel per probe
Summary of Contents for OPW SiteSentinel Integra 100
Page 18: ...Doc M1800 Rev 06 Page 18 of 101 www opwglobal com 2 7 Field Wiring Diagram for Integra 100 ...
Page 19: ...Doc M1800 Rev 06 Page 19 of 101 www opwglobal com ...
Page 20: ...Doc M1800 Rev 06 Page 20 of 101 www opwglobal com 2 8 Field Wiring Diagram for Integra 500 ...
Page 21: ...Doc M1800 Rev 06 Page 21 of 101 www opwglobal com ...
Page 48: ...Doc M1800 Rev 06 Page 48 of 101 www opwglobal com 10 3 3 Flex Probe Determination Worksheet ...
Page 52: ...Doc M1800 Rev 06 Page 52 of 101 www opwglobal com Figure 11 4 Tighten Sensor ...
Page 83: ...Doc M1800 Rev 06 Page 83 of 101 www opwglobal com Appendix H Model 924B Installation Records ...
Page 86: ...Doc M1800 Rev 06 Page 86 of 101 www opwglobal com L048 Overall Length ...
Page 99: ...Doc M1800 Rev 06 Page 99 of 101 www opwglobal com Appendix M Declaration of Conformity ...
Page 100: ...Doc M1800 Rev 06 Page 100 of 101 www opwglobal com ...