: M1800, Rev. 06
Page 35 of 101
www.opwglobal.com
6.2 OM4 Specifications
6.3 OM4 Wiring
1. Follow wiring instructions inside the module for proper Petro-
Net communications and power wiring instruction.
2. Connect all relay wiring to the appropriate terminal block(s).
6.4 OM4 Addressing
CAUTION
: Do not change the module number while the OM4
module power is ON; in addition, no power can be applied to any of
the relay positions.
When installing two or more OM4 Output Module boxes, place the
address jumpers on the OM4 circuit boards as shown below.
1. Take off the four (4) nuts securing the aluminum cover and
remove it, exposing the circuit board.
2. Set the jumpers.
3. Replace the cover.
Petro-Net
Jumper
Shown on
Address #2
•
•
•
•
•
•
•
•
•
•
•
•
Address #1
Address #2
•
•
•
•
•
•
•
•
•
•
Address #3
Address #4
Not Used
Not Used
Not Used
Not Used
Figure 6-2 OM4 Wiring Connections
Figure 6-3 OM4 Addressing
Summary of Contents for OPW SiteSentinel Integra 100
Page 18: ...Doc M1800 Rev 06 Page 18 of 101 www opwglobal com 2 7 Field Wiring Diagram for Integra 100 ...
Page 19: ...Doc M1800 Rev 06 Page 19 of 101 www opwglobal com ...
Page 20: ...Doc M1800 Rev 06 Page 20 of 101 www opwglobal com 2 8 Field Wiring Diagram for Integra 500 ...
Page 21: ...Doc M1800 Rev 06 Page 21 of 101 www opwglobal com ...
Page 48: ...Doc M1800 Rev 06 Page 48 of 101 www opwglobal com 10 3 3 Flex Probe Determination Worksheet ...
Page 52: ...Doc M1800 Rev 06 Page 52 of 101 www opwglobal com Figure 11 4 Tighten Sensor ...
Page 83: ...Doc M1800 Rev 06 Page 83 of 101 www opwglobal com Appendix H Model 924B Installation Records ...
Page 86: ...Doc M1800 Rev 06 Page 86 of 101 www opwglobal com L048 Overall Length ...
Page 99: ...Doc M1800 Rev 06 Page 99 of 101 www opwglobal com Appendix M Declaration of Conformity ...
Page 100: ...Doc M1800 Rev 06 Page 100 of 101 www opwglobal com ...