12.4 Interstitial Sensor
Interstitial Sensors can be installed around the inside perimeter of the
retaining wall or “snaked” under the length of an above ground
storage tank within the retaining wall area.
Interstitial Sensors can also be installed in manways, in trenches or
inside a sump.
12.4.1
Interstitial Sensor Installation
1. Place the Interstitial Sensor in its intended location.
When installing the sensor in a sump, place the
sensor at the bottom of the sump.
2. Connect the sensor to the I.S. Barrier by splicing the
sensor wires to field wires. These wires, in turn, pass
through vapor seal-offs and enter the VSmart Module.
3. Keep track of sensor-wiring identity to ensure proper
wiring at the VSmart Module. A below-grade wiring
workbox can be used as a junction box for the splice
when wiring underground. Follow all applicable
codes.
4. Run separate wiring from each sensor to the chain
leading to the VSmart Module if using the multi-drop
connection method; otherwise, run separate wire for
each sensor.
NOTE
: Probe cables and sensor wiring can share the same conduit.
Keep track of sensor-wiring identity to ensure proper wiring at the I.S.
Barrier.
Figure 12-2 Interstitial Sensor Installed in AST
Figure 12-3 Interstitial Sensor Installed in Manway
Summary of Contents for OPW SiteSentinel Integra 100
Page 18: ...Doc M1800 Rev 06 Page 18 of 101 www opwglobal com 2 7 Field Wiring Diagram for Integra 100 ...
Page 19: ...Doc M1800 Rev 06 Page 19 of 101 www opwglobal com ...
Page 20: ...Doc M1800 Rev 06 Page 20 of 101 www opwglobal com 2 8 Field Wiring Diagram for Integra 500 ...
Page 21: ...Doc M1800 Rev 06 Page 21 of 101 www opwglobal com ...
Page 48: ...Doc M1800 Rev 06 Page 48 of 101 www opwglobal com 10 3 3 Flex Probe Determination Worksheet ...
Page 52: ...Doc M1800 Rev 06 Page 52 of 101 www opwglobal com Figure 11 4 Tighten Sensor ...
Page 83: ...Doc M1800 Rev 06 Page 83 of 101 www opwglobal com Appendix H Model 924B Installation Records ...
Page 86: ...Doc M1800 Rev 06 Page 86 of 101 www opwglobal com L048 Overall Length ...
Page 99: ...Doc M1800 Rev 06 Page 99 of 101 www opwglobal com Appendix M Declaration of Conformity ...
Page 100: ...Doc M1800 Rev 06 Page 100 of 101 www opwglobal com ...